![VOKERA Syntesi e Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/vokera/syntesi-e/syntesi-e_installation-and-servicing-instructions-manual_1044957031.webp)
Supplied By www.heating spares.co Tel. 0161 620 6677
29
Fault code
Possible causes
01
Gas supply problem
Gas line requires purging
Reversed polarity
Broken, internal flue joint
02
Flow/return valves closed
Stuck pump
03
Debris in flue system
Debris in flue venturi
04
Insufficient water pressure
Air in boiler
7.7
ELECTRICAL CHECKS
Any electrical checks must be carried out by a
suitably qualified person.
7.7.1
EARTH CONTINUITY TEST
Isolate the appliance from the electrical supply,
and using a suitable multi-meter carry out a
resistance test. Connect test leads between an
appliance earth point and the earth wire of the
appliance supply cable. The resistance should
be less than 1 OHM. If the resistance is greater
than 1 OHM check all earth wires and connectors
for continuity and integrity.
7.7.2
SHORT CIRCUIT CHECK
Isolate the appliance from the electrical supply, and
using a suitable multi-meter, carry out a short circuit
test between the Live & Neutral connections at the
appliance terminal strip (fig.16).
Repeat above test on the Live & Earth connections
at the appliance terminal strip (fig.16).
NOTE
Should it be found that the fuse has failed but no
fault is indicated, a detailed continuity.
Check will be required to trace the fault. A visual
inspection of components may also assist in
locating the fault.
7.7.3
POLARITY CHECK
With the appliance connected to the electrical
supply and using a suitable multimeter, carry out
the following voltage tests:
●
connect test leads between the Live & Neutral
connections at the appliance terminal strip
(fig.16). The meter should read approximately
230V ac. If so proceed to next stage. If not,
see 7.7.4.
●
connect test leads between the Live & Earth
connections at the appliance terminal strip
(fig.16). The meter should read approximately
230V ac. Iff so proceed to next stage. If not,
see 7.7.4.
●
connect test leads between the Neutral & Earth
connections at the appliance terminal strip
(fig.16). The meter should read approximately
0 – 15Vac. If so polarity is correct. If not, see
7.7.4.
7.7.4
REVERSED POLARITY OR SUPPLY FAULT
Repeat the above tests at the appliance isolator,
if testing reveals correct polarity and/or supply at
the isolator, re-check wiring and connections
between the isolator and the appliance.
If tests on the isolator also reveal reversed polarity
Fig. 46
Protecting
cap
Air analysis outlet
Fumes analysis outlet
●
Light the boiler as described in 5.7 and press
the ‘CO mode’ button once.
●
The boiler will now enter the combustion
analysis mode (CO mode) for a period of 15
minutes. During this time it will remain on full
gas and ‘CO’ will be displayed on the LED
display.
●
Once the flue gas analysis has been made,
press the ‘CO mode’ to resume normal
operation.
7.5
CHECKING THE EXPANSION VESSEL
Carry out the component removal procedure as
described in 6.4. You must ensure that the boiler
is completely drained of water.
Using a suitable pressure gauge, remove dust
cap on expansion vessel and check the charge
pressure. The correct charge pressure should be
1.0 bar
±
0.1 bar.
If the charge pressure is less, use a suitable pump
to increase the charge.
NOTE
You must ensure the safety valve is in the open
position whilst re-charging takes place. Replace
the dust cap and carry out the relevant
commissioning procedure (section 5).
7.6
EXTERNAL FAULTS
Before carrying out any faultfinding or component
replacement, ensure the fault is not attributable
to any aspect of the installation.
7.6.1 INSTALLATION FAULTS
Symptom
Possible causes
No ignition
Check wiring
Check electrical supply
No hot water
Check hot/cold pipe
work is not reversed
No central heating
Check wiring of time clock
and/or room thermostat