background image

18

5.1

GAS SUPPLY INSTALLATION

Inspect the entire installation including the gas
meter, test for soundness and purge. Refer to BS
6891 for specific instruction.

5.2

THE HEATING SYSTEM

The appliance contains components that may
become damaged or rendered inoperable by oils
and/or debris that are residual from the installation
of the system, consequently it is essential that the
system be flushed in accordance with the follow-
ing instructions.

5.3

INITIAL FILLING OF THE SYSTEM

Ensure both flow and return service valves are
open, remove appliance casing as described in
4.7.1, identify the automatic air release valves
(AAV) and loosen the dust cap/s by turning the cap
anti-clockwise one full turn.
IMPORTANT, THERE ARE NO MANUAL AIR
RELEASE VALVES LOCATED ON THE APPLI-
ANCE. Ensure all manual air release valves lo-
cated on the heating system are closed.
Connect the filling loop as shown in fig. 6B, slowly
proceed to fill the system by firstly opening the
inlet valve connected to the flow valve, and then
turning the lever on the combined stopcock and
check valve, to the filling position (see fig. 18). As
water enters the system the pressure gauge will
begin to rise. Once the gauge has reached 1 BAR
close both valves and begin venting all manual air
release valves, starting at the lowest first. It may
be necessary to go back and top-up the pressure
until the entire system has been filled.  Inspect the
system for water soundness, rectifying any leaks.

5.4

INITIAL FLUSHING OF THE SYSTEM

The whole of the heating system must be flushed
both cold and hot as detailed in 5.8. Open all
radiator or heating valves and the appliance flow &
return service valve. Drain the boiler and system
from the lowest points. Open the drain valve full
bore to remove any installation debris from the
boiler prior to lighting. Refill the boiler and heating
system as described in 5.3.

5.5

FILLING THE HOT WATER SYSTEM

Close all hot water outlets, turn appliance stop-
cock to the normal operating position (fig. 18),
slowly open each outlet until air has been expelled
and clear water is discharged.
Check pipe-work etc. for water soundness.

5.6

PRE-OPERATION CHECKS

Before attempting the initial lighting of the appli-
ance, the following checks must be carried out:

ensure all gas service valves from the meter to
the appliance are open and the supply pipe has
been properly purged;

ensure the proper electrical checks have been
carried out, (see 7.8) particularly continuity,
polarity, and resistance to earth;

ensure the 3 AMP fuse – supplied with the
appliance – has been fitted;

ensure the system has been filled, vented, and
the pressure set to 1 BAR;

ensure the flue system has been fitted properly
and in accordance with the instructions;

ensure all appliance service valves are open.

5.7

INITIAL LIGHTING

Ensure the electrical supply to the appliance is
switched on.  Press the ON/OFF switch to switch
the appliance ON (indicated by active display),
ensure any external controls are switched to an
‘ON’ position and are calling for heat.
Press the function button and select 

Winter mode,

the appliance will now operate in the 

Winter mode

as described in 1.2. Should the appliance fail to
ignite, refer to 5.6 and/or section 7 (mode of
operation, parameter setting, & faultfinding).

5.7.1

CHECKING GAS PRESSURE AND COMBUS-
TION ANALYSIS

The appliance is factory set and requires no
additional adjustment once installed.However to
satisfy the requirements of GSIUR 26/9 (I.S. 813
ROI), it will be necessary togas rate the appliance
using the gas meter that serves the appliance.If
the installation does not include a gas meter (for
example LPG) and there are nomeans by which
to calculate the gas rate, then a combustion
analysis test must becarried out in accordance
with BS 7967 (UK) to ensure the appliance is left
workingsafely and correctly.Additionally, if the gas
valve has been adjusted, replaced, or the
appliance has beenconverted for use with another
gas type, then it becomes necessary to carry out
acombustion analysis/check to ensure that
correct combustion is occurring.If there are no
means to gas rate the appliance and/or carry out
a combustion analysischeck, then it will not be
possible to complete the commissioning proce-
dure. Details on how to carry out the combustion
analysis can be found in section 7.

IMPORTANT

It’s imperative that a sufficient dynamic – gas –
pressure is maintained at all times.Should the
dynamic gas pressure fall below an acceptable
level, the appliance maymalfunction or sustain
damage

5.8

FINAL FLUSHING OF THE HEATING SYSTEM

The system shall be flushed in accordance with
BS 7593. Should a cleanser be used, it must be
suitable for Copper and Aluminium heat exchang-

SECTION 5      COMMISSIONING

normal op-
erating posi-
tion

filling posi-
tion

closed
position

Fig. 18

Содержание Linea Max HE

Страница 1: ...SE INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK...

Страница 2: ...3 1 2 Mode of operation 3 1 3 Mode of operation Heating 3 1 4 Mode of operation DHW 3 1 5 Safety devices 3 1 6 Optional accessories 3 Technicaldata Page 2 1 Central heating 4 2 2 Domestic hot water 4...

Страница 3: ...s is comprised of 3 models of high efficiency combination boiler with in puts to heating DHW of 25 30 30 35 and 35 35 kW respectively Each appliance by design incorporates electronic ignition circulat...

Страница 4: ...ater temperature control current water pressure outside sensor currentappliancetemperature error code current mode of operation burner on frost protection on Symbolsdescription Summer Spring Autumn Wi...

Страница 5: ...or DHW via a hot water outletortap thepumpandfanarestarted thefan speedwillmodulateuntilthecorrectsignalvoltage is received at the control PCB At this point an ignition sequence is enabled Ignition is...

Страница 6: ...min output rpm 1 400 1 400 1 400 2 4 Expansion Vessel Capacity 10 litres 10 litres 10 litres Maximum system volume 91 litres 91 litres 91 litres Pre charge pressure 1 0 bar 2 5 Dimensions Height 845 m...

Страница 7: ...m an opening in the car port into the building 1200 mm M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm P From a structure to the side of th...

Страница 8: ...nt cupboarddesignincludingairingcupboardinstal lations are given in BS 6798 This appliance is not suitable for external installation 3 3 GAS SUPPLY The gas meter as supplied by the gas supplier must b...

Страница 9: ...pacity see 6 24 3 6 6 FILLING POINT A method for initial filling of the system and replacingwaterlostduringservicingetc hasbeen provided This method of filling complies with the currentWaterSupply Wat...

Страница 10: ...strict accordance with the manufacturers instructions Water treatment of the complete heating system including the boiler should be carried out in accordance with BS 7593 and the DomesticWater Treatm...

Страница 11: ...stion products is not impeded and with due regard for the damage and discoloration thatmayoccurtobuildingproductslocatednearby The terminal must not be located in a place where it is likely to cause a...

Страница 12: ...le switch with a contact separation of at least 3mm The switch must only supply the appliance and its corresponding con trols i e time clock room thermostat etc 3A 8 SHOWERS If the appliance is intend...

Страница 13: ...outlet permits both horizontal and verticalflueapplicationstobeconsidered alterna tively the Vokera twin flue system can be utilised if longer flue runs are required 4 5 1 CONCENTRIC HORIZONTAL FLUE...

Страница 14: ...iance NOTE When cutting an extension to the required length you must ensure that the excess is cut from the plain end of the extension see fig 7 8 Re move any burrs and check that all seals are lo cat...

Страница 15: ...edi cated concentric flue kit for termination It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions GUIDANCE NOTES ONTWIN FLUE INSTA...

Страница 16: ...orizontal flue terminal ensuring that there is a 1 fall back to the boiler 17mm per 1000mm Insert the terminal assembly into the flue hole Push fit the twin flue pipes onto the concentric to twin conv...

Страница 17: ...o adjust the pitch of the fixing jig to compen satefortheincreaseinthedepthoftheappliance The appliance is supplied with a fixing jig that includes service valves fig 14 The service valvesareofthecomp...

Страница 18: ...ensureitdischargesinaccord ance with building regulations or other rules in force 4 7 ELECTRICALCONNECTIONS The electrical supply must be as specified in section 3 3A A qualified electrician should co...

Страница 19: ...erminal block Connect the EARTH wire to the EARTH block see fig 17 ensuring that it s left slightly longer that the others this will prevent strain on the EARTH wire should the cable become taut Do no...

Страница 20: ...appliance are open and the supply pipe has beenproperlypurged ensure the proper electrical checks have been carried out see 7 8 particularly continuity polarity and resistance to earth ensure the 3 AM...

Страница 21: ...efer to section 7 5 10 SETTING THE SYSTEM DESIGN PRESSURE The design pressure should be a minimum of 0 5 BAR and a maximum of 1 5 BAR The actual reading should ideally be 1 BAR plus the equivalent hei...

Страница 22: ...mentation supplied with this appli ance including these instructions and explain the importance of keeping them in a safe place Explain to the user how to isolate the appliance from the gas water and...

Страница 23: ...anandfreefromanydebrisorobstruction Check and clean if necessary the condense trap to ensure correct operation 6 3 REPLACEMENTOFCOMPONENTS Although it is anticipated that this appliance will give year...

Страница 24: ...or electrical plug Replace in the reverse order 6 10 RETURN THERMISTOR fig 1 Carry out component removal procedure as de scribed in 6 4 Unclip and remove the air chamber front cover Unclip the return...

Страница 25: ...all seals are in good condition taking care to ensure they are replacedcorrectly 6 15 BURNER fig 32 Carry out component removal procedure as de scribed in 6 4 Unclip and remove the air chamber front...

Страница 26: ...o ensure they are replaced correctly 6 20 VALVE ACTUATOR fig 36 Carry out component removal procedure as described in 6 4 Remove the locking pin F that secures the actuator G to the heating manifold D...

Страница 27: ...on heat shrinkable insulators that protect the transformer connec tors Unthread the heat shrinkable insulators Carefully remove the fan transformer Replace in the reverse order ATTENTIONThetransformer...

Страница 28: ...FUNCTIONS DHW pre heat this function is only active when there are no requests for heating or hot water The pre heat function has priority on CH request When the secondary thermistor drops to 35 C th...

Страница 29: ...an may continue to circulate to dissipate any residual heat within the appliance 7 2 8 DHWMODE When the ON OFF selector is in the ON position and a DHW outlet is opened the appliance will operate in t...

Страница 30: ...output CH fan speed rpm 36 3600 1 25 Differential heating positive C 2 10 1 6 26 Differential heating negative C 2 10 1 6 28 CH timer force burner 75 after CH start Min 0 20 1 15 29 CH timer blocking...

Страница 31: ...he electrical supply and remove the appliance casing as described in 4 7 1 Set the flue gas analyser to read CO2 and inserttheprobeintotheflueanalysistestpoint A B fig 40 Restore the electrical supply...

Страница 32: ...epeat above test on the Live Earth connec tions at the appliance terminal strip fig 17 NOTE Shoulditbefoundthatthefusehasfailedbutnofault is indicated a detailed continuity check will be required to t...

Страница 33: ...T CODE 9x Fault codes 9x appear if the condense trap pipe has become blocked Ensure the condense trap is clear Ensure the condense pipe is clear NOTE Restore the electrical supply to the boiler and tu...

Страница 34: ...8 3 VOKERA ROOMTHERMOSTAT Connect the Vokera room thermostat to the appliance as detailed in fig 45 The Vokera room thermostat can be used as detailed in fig 46 8 4 OTHER DEVICES Fig 47 details typic...

Страница 35: ...SC1 Sparking transformer TR1 Main transformer O S Outside sensor WPS Water pressure sensor FS Flow termoster RS Return termoster AE01A P1 Master board AE01A P2 Ausiliary board control M0T2B Motor cont...

Страница 36: ...pressuresensor Underflowsystemoverheattemperature RS232 PC interface Displayboardconnection AE01A P1connection AE01A P1connection Unused Unused Unused PCB AE01A P1 AE01A P1 AE01A P1 AE01A P1 AE01A P1...

Страница 37: ...0025842 10025842 26 Instrumental panel 10029365 10029365 10029365 31 Case 10026241 10026241 10026241 38 Driver PCB 10027200 10027200 10027200 90 Fuse 3478 3478 3478 226 Edge clip 5128 5128 5128 300 Wi...

Страница 38: ...024643 48 Discharge cock 10024646 10024646 10024646 50 Connections cover 10027685 10027685 10027685 61 Non return valve 10023569 10023569 10023569 62 Filling cock 10023568 10023568 10023568 63 Pipe 10...

Страница 39: ...25 Siphon 10027190 10027190 10027190 26 Flexible pipe 10027191 10027191 10027191 27 Flexible pipe 10027192 10027192 10027192 66 Flexible pipe 10026272 10026272 10026272 69 Pressure gauge 10027135 100...

Страница 40: ...0026309 39 Gas pipe 10026317 10026698 10027196 67 Washer 10026322 10026322 10026322 69 Tryton 10027089 10027089 10027089 72 Mixer 10024295 10024295 10024295 200 Washer R5023 5023 5023 328 Clip 1890 18...

Страница 41: ...369 7 Conveyor assembly 10026310 10026310 10026310 12 Flue drain connection 10028421 10028421 10028421 475 Washer 10026323 10026323 10026323 482 Washer 10026366 10026366 10026366 487 Washer 10026345 1...

Страница 42: ...ent screw see fig 43 clock wisetodecrease counterclockwisetoincrease until the correct value is displayed on the CO2 analyser allow time for the analyser to stabilise IMPORTANT A GAS SOUNDNESS CHECK M...

Страница 43: ...HOT WATER OUTLET TEMPERATURE C WATER FLOW RATE lts min FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS YES...

Страница 44: ...CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No...

Страница 45: ...Note...

Страница 46: ...Note...

Страница 47: ......

Страница 48: ...ra co uk www vokera ie Sales General Enquires T 0844 391 099 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the right to change specifi...

Отзывы: