Pre-set curves

There are six available curves fro heating and two for cooling, accessible 
through parameters 112 and 117 in the installer’s configuration table.

The curves are set so as to maintain and indoor temperature of 20°C.
When the external temperature reaches 20°C, the units stops providing 
either heating or cooling.

1

Heating

2

Cooling

x

Outdoor temperature

Y

Water temperature

1

2

3

4

5

6

15

20

25

30

35

40

45

50

55

60

65

-15

-10

-5

0

5

10

15

20

25

°C 

°C 

Fan Coil

x

y

x

y

1

1

15

-20

-15

-10

-5

0

5

10

15

20

25

°C

°C

20

25

30

35

40

45

50

55

60

65

7

8

9

10

11

12

1

2

0

5

10

15

20

15

20

25

30

35

40

45

°C 

°C 

x

y

x

2

Customised Climate Curves.

Parameters 112 and 117 set at zero make it possible to load a customised 
curve in the control.

The pictures show which parameters in the installer’s configuration table 
must be set to create the customised climate curves for heating and 
cooling.

1

Heating

2

Cooling

x

Outdoor temperature

Y

Water temperature

x

x

y

y

1

2

0

5

10

15

20

15

20

25

30

35

40

45

par 4

1

2

3

4

15

25

35

45

55

65

-15

-10

-5

0

5

10

15

20

25

par 4

1

2

3

4

1 - MAX W T° W1  

(Par No 121)

2 - NO HEAT T° W1  (Par No 120)
3 - REGION T° O  

(Par No 118)

4 - STOP H T° O  

(Par No 119)

1 - MAX COOL W T°  (Par No 125)
2 - MIN COOL W T°   (Par No 124)
3 - COOL STOP T°  

(Par No 123)

4 - MAX REGION T°   (Par No 122) 

  

 
 

 28

  

Содержание AriaPRO 004 M

Страница 1: ...ctions Installation Servicing Instructions THESEINSTRUCTIONS TOBERETAINED BYUSER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioni...

Страница 2: ...2...

Страница 3: ...modify or tamper with this equipment as doing so might cause dangerous situation for which the manufacturer waives all liability In the installation and or maintenance operations please adopt the appr...

Страница 4: ...ance Climate control Titolo_fittizio The AriaPRO range units are designed for the production of refrigerated water for air conditioning heated water for heating and sanitary hot water for homes reside...

Страница 5: ...4 4 Energy class 7 B Generalities Sound pressure in heating 1 dB A 42 44 47 48 Sound pressure in cooling 7 dB A 44 45 48 49 Compressor Rotary DC Inverter Tecnology R410a refrigerant charge kg 1 195 1...

Страница 6: ...hot water production may be limited according to the settings of the safety devices in the equipment For technical activities please refer to the technical tag mounted on board the machine It is forbi...

Страница 7: ...44 1 8 2 16 2 52 2 88 3 24 10 20 30 40 50 60 70 80 90 A B AriaPro 006 M AriaPro 004 M AriaPro 008 M AriaPro 012 M 015 M 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 0 2 0 3 0 4 0 5 0 1 0 0 Dimensions Ti...

Страница 8: ...2 1 49CF 2 1 50CF 3 2 1 51CF 2 1 3 L N PE 1TS 1TO 1TD 1TE 1PMV 004 M Power Wiring of the manufacturer Field wiring CM Compressor motor FM Fan engine RV Reversing valve 4 way TS Probe temperature low p...

Страница 9: ...1 2 31CF 1 2 32CF 7 6 5 4 3 2 1 33CF 1 2 3 4 5 6 34CF 7 6 5 4 3 2 1 35CF 1 2 3 4 36CF 1 2 3 4 5 6 37CF 1 2 3 4 5 3TB C W G Y 23 24 1 2TB N 18 10 11 12 5TB 21 22 3 6 7 8 2 4TB 4 5 16 13 14 15 N 38CF 1...

Страница 10: ...10 J4 1 2 03 J3 1 2 08 J1 1 1FM 1CM R S C 40CF 1 2 3 7CM 1 2 3 1R 41CF 2 1 8CM 2 1 2T 1 2 P25 P24 P23 P22 P21 P20 P35 P34 P19 P18 P04 P05 P06 1P C BOARD P11 P08 1MCC 1530 42CF 1 2 3 43CF 1 2 3 P33 P32...

Страница 11: ...1 2 31CF 1 2 32CF 7 6 5 4 3 2 1 33CF 1 2 3 4 5 6 34CF 7 6 5 4 3 2 1 35CF 1 2 3 4 36CF 1 2 3 4 5 6 37CF 1 2 3 4 5 3TB C W G Y 23 24 1 2TB N 18 10 11 12 5TB 21 22 3 6 7 8 2 4TB 4 5 16 13 14 15 N 38CF 1...

Страница 12: ...1 50Hz 1FM 6CM R S C 40CF 1 2 3 7CM 1 2 3 1R 41CF 2 1 8CM 2 1 2T 1 2 P25 P24 P23 P22 P21 P20 P35 P34 P19 P18 P04 P05 P06 1P C BOARD P11 P08 1MCC 1530 42CF 1 2 3 43CF 1 2 3 P33 P32 2R 44CF 2 1 9CM 2 1...

Страница 13: ...J6B 1 J6B 2 J6B 1 J6B 2 J18 1 J18 2 J11 7 J11 6 J11 5 J11 4 J11 3 J11 2 J11 1 10 58CF 1 2 3 4 5 6 J16 1 J16 2 59CF 1 2 3 4 5 J5 1 11 J16 3 J5 2 J16 4 J5 3 12 J16 5 J5 4 J16 6 3TB J5 5 C 60CF 7 6 5 4...

Страница 14: ...PE 1F 1 2 L 1RV N 39CF 1 2 3 40CF 1 2 3 4 5 CN01 CN02 CN03 1P C BOARD 2P C BOARD 7CM 1 2 3 41CF 1 2 3 P08 42CF 1 2 3 4 5 43CF 1 2 3 4 5 1PVM 44CF 1 2 3 4 5 6 2TB P09 8CM 1 2 3 45CF 1 2 3 P12 P13 46CF...

Страница 15: ...1 J6B 2 J6B 1 J6B 2 J18 1 J18 2 J11 7 J11 6 J11 5 J11 4 J11 3 J11 2 J11 1 10 68CF 1 2 3 4 5 6 J16 1 J16 2 69CF 1 2 3 4 5 J5 1 11 J16 3 J5 2 J16 4 J5 3 12 J16 5 J5 4 J16 6 4TB J5 5 C 70CF 7 6 5 4 3 2 1...

Страница 16: ...SW801 CN704 BLUE SW800 RY704 P04 CN701 WHITE P05 CONTROL P C BOARD MCC 1571 P06 CN04 WHITE P07 CN200 F03 T10A 250V F01 T25A 250V CN201 P01 L F P02 CN202 P09 1TB 2TB 1 2 3 J4 1 2 10 J3 1 2 03 J1 1 2 08...

Страница 17: ...F 1 2 31CF 1 2 32CF 7 6 5 4 3 2 1 33CF 1 2 3 4 5 6 34CF 7 6 5 4 3 2 1 35CF 1 2 3 4 36CF 1 2 3 4 5 6 37CF 1 2 3 4 5 4TB C W G Y 23 24 1 3TB N 18 10 11 12 6TB 21 3 6 7 8 2 5TB 4 5 16 13 14 15 N 38CF 1 2...

Страница 18: ...entially hazardous packaging materials within the reach of children Scope of supply Also supplied Installer manual External probe Barcode labels Control panel Strain relief size 015M only List of spar...

Страница 19: ...discomfort That the airflow from the unit is opposed by a contrary wind The units must Be placed on a level surface able to support their weight Be placed on a sufficiently rigid floor slab that does...

Страница 20: ...ing agents or subject to special regulations require the use of water disconnectors Failure to install filters flow meter and anti vibrating mounts can cause obstruction breakage and noise issues for...

Страница 21: ...Ground the unit thoroughly At the end of the connections fasten the cables with the appropriate cable glands and replace the terminal boxes covers Do not use gas and water pipes to ground the unit Co...

Страница 22: ...aximum length of the connecting cable must be taken into account Use a shielded cable for the connection The connection cable must not be spliced if splicing is necessary it shall be tinned and adequa...

Страница 23: ...r s oil to warm up Position the remote switch if present in the on position Start the equipment according to the directions in the control panel section Checks during and after the first commissioning...

Страница 24: ...indoors can generate toxic gases if they come into contact with naked flames or high temperature bodies in case of leaks please air the rooms thoroughly Do not charge the refrigerating circuits with a...

Страница 25: ...d time START TIME Activates the programming menu displaying the beginning of the six periods of time scheduled PERIOD Activates the programming menu displaying the six periods of time scheduled DAYS A...

Страница 26: ...nge parameter Activate the arrow keys Set the current value Push the OK key to confirm Setting of room temperature Push the mode key Select the desired operation mode Activate the arrow keys Set the d...

Страница 27: ...you press the OK key the settings shall be saved and the value of the parameter shall start blinking with the possibility of changing it later on If you press the Mode key the settings shall be saved...

Страница 28: ...50 55 60 65 7 8 9 10 11 12 1 2 0 5 10 15 20 15 20 25 30 35 40 45 C C x y x 2 Customised Climate Curves Parameters 112 and 117 set at zero make it possible to load a customised curve in the control Th...

Страница 29: ...etition of the abnormal operation requires an accurate check of the unit s components Before resetting it is necessary to remove the cause of the anomaly Abnormal operations are notified by the Contro...

Страница 30: ...ompressor disorder etc Discharge temp error Power supply error Heat sink overheat error Gas leak detection 4 way valve reverse error High pressure protective operation Fan system error Driving element...

Страница 31: ...he arrow for Sleep 12 C 38 C 26 C Away heat t 19 AWAY Temperature set point in Heating mode C and the arrow for Away 12 C 38 C 15 C Away cool t 20 AWAY Temperature set point in Cooling Mode C and the...

Страница 32: ...k Max compressor fre quency 132 This code displays the maximum compressor frequency calculated by GMC control board Lock Requested frequency 133 This code displays the requested frequency by the syste...

Страница 33: ...al wp logic 156 This code is use to select the output connected at PIN 11 on terminal strip In case an additional water pump option is active this code is use to select its operating logic vs the SHW...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited res...

Отзывы: