Description: Device Setup
Data type: UINT16
Selection of the controller mode and the source of the set
point.
As example if you want to switch between flow or pressure control and vis versa, with value = “1” we
would control flow, and with value =”5” we would regulate pressure
Value Description
0
Automatic set point selection
The source of set point is automatically selected, i.e.: As standard the analog set point (voltage or
current signal) is active. If a digital set point is sent (via ModBus) automatically the red-y switches
to ‘Digital mode’ and the analog set point is disabled.
1
Digital set point
Activates the digital set point via digital communication (ModBus, PROFINET)
2
Analog set point (standard setting)
Selects the analog signal as set point source.
5
Pressure controller activated
6
Back pressure controller activated
10
Direct adjustment of the valve signal
Deactivates the automatic control mode. Sets the valve control to the value of register ‘valve
power´
20
Set point 0%
Sets the set point to 0%.
21
Set point 100%
Sets the set point to 100%.
22
Valve fully closed
Deactivates the automatic control mode. Sets the valve control to 0% (Valve fully closed).
23
Valve fully open
Deactivates the automatic control mode. Sets the valve control signal to 100% (Valve fully open).