P18AL Service Manual
TROUBLESHOOTING
3/6/07
8-6
Symptom: High suction pressure (check gage accuracy)
Possible Cause
Possible Remedy
Compressor running unloaded or not pumping efficiently
Check compressor motor amp. If the compressor is running
unloaded, the amperage will only be approximately 60% of
normal amp draw. Refer to the compressor manual.
Thaw gas valve (18) leaking through
Make sure manual opening stem is in the automatic (screwed
in) position. Repair or replace defective parts.
Suction Pressure to low
Adjust suction regulator valve
Defective gage
Check pressure with accurate gage and replace as necessary.
Symptom: Compressor running unloaded during freeze (dedicated compressor only)
Possible Cause
Possible Remedy
Low oil pressure
Check compressor net oil pressure.
Net oil pressure = oil pressure gage reading less suction
pressure.
Mycom = 17-28 psig
Vilter = 35-50 psig.
Refer to the compressor manual for “Oil Pressure
Adjustment”.
Unloader solenoid valve open
Check solenoid coil to make sure it is not energized. If valve
is stuck open, replace valve.
Unloader mechanism not working properly
Refer to compressor manual. Mycom compressor can be
loaded manually.
Symptom: Compressor oil pressure low (check gages)
See Section 7, for compressor oil pressure requirements.
Possible Cause
Possible Remedy
Oil diluted with refrigerant
Oil will be very foamy. Check liquid feed control for overfeed
problem.
Oil pressure regulating valve out of adjustment
Adjust valve to increase oil pressure. Turn stem in to increase,
out to decrease.
Compressor rotation incorrect
Check rotation direction by arrow indication. Reverse
rotation, if necessary.
Restriction strainer, oil filter, pick-up tube or oil passage
Clean strainer or restriction in passage or replace filter.
Compressor thrust bearing installed upside down
The Mycom compressor thrust bearing on the shaft seal end
has an oil passage hole that has to be in the proper position
when installing the thrust bearing. Hole up for “WA” and
“WB” series Mycom compressor. Refer to your compressor
manual.
Symptom: Compressor loosing oil excessively
Possible Cause
Possible Remedy
Non-effective oil separator or float
The oil separator will normally return a good portion of oil
leaving the compressor, if it is working properly. Check the
oil float and return line to see it is not restricted.
Liquid refrigerant in crankcase
Check liquid feed to make sure it is not overfeeding and that
the solenoid valve (25) is not leaking through when the
machine is stopped.
Compressor piston rings seized or broken
Check compressor efficiency. If rings are seized or broken,
replace defective parts.
Leaking shaft seal
A few drops per minute is okay. If ammonia is leaking,
replace the seal.
Содержание P18AL TUBE-ICE
Страница 1: ...8 28 00 P18AL TUBE ICE MACHINE Manual Part Number 12A4171M09 Service Manual 5000 ...
Страница 4: ......
Страница 14: ...P18AL Service Manual INTRODUCTION 3 6 07 1 4 FIGURE 1 1 P18AL Front View ...
Страница 15: ...P18AL Service Manual INTRODUCTION 3 6 07 1 5 FIGURE 1 2 P18AL Back View ...
Страница 16: ...P18AL Service Manual INTRODUCTION 3 6 07 1 6 FIGURE 1 3 P18AL Left View ...
Страница 17: ...P18AL Service Manual INTRODUCTION 3 6 07 1 7 FIGURE 1 4 P18AL Right View ...
Страница 18: ...P18AL Service Manual INTRODUCTION 3 6 07 1 8 ...
Страница 25: ...P18AL Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 6 07 3 5 FIGURE 3 1 Spacing and Connection Diagram ...
Страница 27: ...P18AL Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 6 07 3 7 FIGURE 3 3 Piping Schematic Central High Side ...
Страница 47: ...P18AL Service Manual ELECTRICAL CONTROLS 3 6 07 6 5 FIGURE 6 3 Electrical Schematic All Voltages 50 60 Hz ...
Страница 48: ...P18AL Service Manual ELECTRICAL CONTROLS 3 6 07 6 6 ...
Страница 56: ...P18AL Service Manual MAINTENANCE 3 6 07 7 8 ...
Страница 64: ...P18AL Service Manual TROUBLESHOOTING 3 6 07 8 8 ...
Страница 76: ...P18AL Service Manual SERVICE OPERATIONS 3 6 07 9 12 FIGURE 9 3 Cutter Water Tank Assembly ...
Страница 78: ...P18AL Service Manual TABLES CHARTS 3 6 07 10 1 10 Tables Charts ...