P18AL Service Manual
TROUBLESHOOTING
3/6/07
8-5
Symptom: Poor ice quality
Possible Cause
Possible Remedy
Excessive concentration of solids in the water tank usually
indicated by a build-up of mineral deposit on the sides and
bottom of the tank and opaque ice production. Also, water
distributors restricted.
Perform a cleaning procedure as well as removing the freezer
cover and cleaning the water distributors. Make sure the
flushing valve (27) is functioning and the tank overflow piping
is not restricted.
Insufficient water supply indicated by a low level in the tank
Check water pressure, 30 psig is recommended minimum.
Check for a water line restriction, partially closed valve, or
defective make-up water float valve. Make sure the water tank
drain is closed.
Water pump rotation wrong direction
Check rotation in relation with arrow on pump housing and
reverse two wires at the motor if necessary.
Low refrigerant charge, causing an ice out problem and re-
freeze
Check refrigerant level mark on the receiver and on the painted
portion of the gage glass guard. Be sure to keep the gage glass
cocks closed when finished checking the level.
Suction Pressure to low
Adjust suction regulator valve
Restriction in liquid line, causing short freeze cycle
Check for closed valve, defective solenoid valve (25), float
switch defective or strainer restricted. The liquid line will
normally have frost on the down-stream side of a restriction,
especially as the suction pressure decreases.
Symptom: High discharge pressure (check gage accuracy)
Possible Cause
Possible Remedy
Insufficient water flow through the cooling tower or condenser
Check the condenser water pump to make sure it is pumping
enough water. Check sump strainer screen and clean. Check
condenser pump direction of rotation.
Fan control out of adjustment
Check adjustment. Replace if defective.
Non-condensable in system.
If non-condensables are present with the refrigerant, the
saturated temperature will not relate to the pressure reading at
the receiver. The refrigerant will be cooler, although the
pressure will be high. Air can be purged from the system by
following instructions in Section 9, “Purging Non-
Condensables”.
Cooling tower or evaporative condenser requires maintenance
Check fan motor and fan belts for proper operation and
tension. Check spray nozzles, tubes, sump, and sump screen,
for accumulation of mineral deposit and clean as required.
Check tower blowdown and chemical treatment if applicable.
Dirty condenser tubes
Visually inspect the condenser tubes to see if there is any
build-up of mineral deposits which would reduce the cooling
effect of the tubes and water. Clean chemically or
mechanically as applicable.
Symptom: Low discharge pressure (check gage accuracy)
Possible Cause
Possible Remedy
Fan cycling switch out of adjustment or defective
Check adjustment. Replace if defective.
Compressor running unloaded or not pumping efficiently
Check compressor motor amp. If the compressor is running
unloaded, the amperage will only be approximately 60% of
normal amp draw (FLA). Refer to the compressor manual.
Ambient temperature low and prevailing winds blowing
through tower
Shield tower from prevailing winds to prevent excessive
cooling. Install an indoor sump.
Too much cold water circulating through condenser
Install a water regulating valve in the water line form the
condenser and control flow by receiver pressure.
Thaw gas valve (18) leaking through
Make sure manual opening stem is in the automatic (screwed
in) position. Repair or replace defective parts.
Содержание P18AL TUBE-ICE
Страница 1: ...8 28 00 P18AL TUBE ICE MACHINE Manual Part Number 12A4171M09 Service Manual 5000 ...
Страница 4: ......
Страница 14: ...P18AL Service Manual INTRODUCTION 3 6 07 1 4 FIGURE 1 1 P18AL Front View ...
Страница 15: ...P18AL Service Manual INTRODUCTION 3 6 07 1 5 FIGURE 1 2 P18AL Back View ...
Страница 16: ...P18AL Service Manual INTRODUCTION 3 6 07 1 6 FIGURE 1 3 P18AL Left View ...
Страница 17: ...P18AL Service Manual INTRODUCTION 3 6 07 1 7 FIGURE 1 4 P18AL Right View ...
Страница 18: ...P18AL Service Manual INTRODUCTION 3 6 07 1 8 ...
Страница 25: ...P18AL Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 6 07 3 5 FIGURE 3 1 Spacing and Connection Diagram ...
Страница 27: ...P18AL Service Manual INSTALLING YOUR TUBE ICE MACHINE 3 6 07 3 7 FIGURE 3 3 Piping Schematic Central High Side ...
Страница 47: ...P18AL Service Manual ELECTRICAL CONTROLS 3 6 07 6 5 FIGURE 6 3 Electrical Schematic All Voltages 50 60 Hz ...
Страница 48: ...P18AL Service Manual ELECTRICAL CONTROLS 3 6 07 6 6 ...
Страница 56: ...P18AL Service Manual MAINTENANCE 3 6 07 7 8 ...
Страница 64: ...P18AL Service Manual TROUBLESHOOTING 3 6 07 8 8 ...
Страница 76: ...P18AL Service Manual SERVICE OPERATIONS 3 6 07 9 12 FIGURE 9 3 Cutter Water Tank Assembly ...
Страница 78: ...P18AL Service Manual TABLES CHARTS 3 6 07 10 1 10 Tables Charts ...