9
CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to combustible materials be strictly adhered to during installation
of the stove. Refer to the tables below :
A
C
E
F
E
B
D
Single Wall Pipe (Double Wall Pipe)
A
B
C
D
E
F
20(14)
(508mm(356mm))
22(20)
(559mm(508mm))
22.5(16.5)
(572mm(419mm))
32(30)
(813mm(762mm))
12(11)
(305mm(279mm))
22(21)
(559mm(533mm))
• Floor to ceiling height must be at least 7’ (2.13m) in all cases.
• Do not place any combustible material within 4’ (1.2m) of the front of the unit.
• The clearance between the
fl
ue pipe and a wall are valid only for vertical walls and for vertical
fl
ue pipe.
• The chimney connector must not pass through an attic or roof space, closet or similar concealed space, a
fl
oor, or a ceiling.
• In Canadian installation where passage through a wall, or partition of combustible construction is desired,
the installation must conform to CAN/CSA-B365.
• A
fl
ue pipe crossing a combustible wall must have a minimum clearance of 18” (457.2mm).
• To reduce
fl
ue clearances from combustible materials, contact your local safety department.