locAtiNG stoVE
1. The stove must be placed on solid concrete, solid
masonry, or when installed on a combustible floor,
on a listed floor protector, such as Hy-C or Impe-
rial Model UL3648BK or equivalent. Floor protector
must be 1/2” minimum thickness (R value = 0.84,
see page 21 for calculation formulas) non-combus-
tible material or equivalent. The base must extend
at least 18” beyond the front of the access door, 6”
to the sides of fuel opening. It must extend under
and 2 inches beyond either side of the stove pipe
if it is elbowed towards a wall. (See figures 5 & 7
and consult local building codes and fire protection
ordinances.)
CAUTION: (FIRE hAzARD) CARPETINg AND
OThER COMBUSTIBLE MATERIAL ShALL
NOT COvER ThE FLOOR PROTECTOR.
ThESE MATERIALS MUST REMAIN OUTSIDE
OF COMBUSTIBLE CLEARANCES, SEE FIg.
5 – 7.
2. The stove must have its own flue.
DO NOT
CONNECT ThIS UNIT TO A ChIMNEY FLUE
SERvINg OThER APPLIANCES.
continued on next page
machine screws using the threaded holes located
in the rear side corners of the stove.
AssEmblY iNstRUctioNs continued…
Fig. 3 – back Heat shield and Deflector Assembly (top
view)
9. Attach the heat shield deflector (#17) to the top of
the back heat shield assembly with three Phillips
head machine screws. The angled lip of the deflec-
tor should face toward the front of the stove.
10. Attach blower assembly to rear of the back heat
shield with four Phillips head machine screws
from the hardware pack. Make sure to position the
ceramic gasket between the back heat shield and
the blower assembly so it does not block the fan
opening.
11. After properly locating floor protector (fig 5) to ac-
commodate minimum stove clearances, place stove
in position on floor protector.
12. Route the power cord away from stove. Do not al-
low the power cord to touch any hot surfaces. Keep
power cord at least 12” from stove surfaces.
13. Check to make sure that the bottom fire bricks (#13)
and ceramic fiber boards (parts #18 & #19) above
the air tube assembly (#6) have not shifted during
shipping or assembly.
14. Once stove is positioned, plug power cord into a
grounded 120v outlet.
Fig. 4 – blower attaches to rear heat deflector
3. After observing the clearances to combus-
tible materials (figures 5–7), locate your floor
protector accordingly (figure 5) and careful-
ly place the stove in your selected location.
Install stove pipe, elbows, and thimble as
required, utilizing either a recently cleaned and
inspected 6” masonry chimney or a 6” i.d. listed
type HT chimney.
4. Use round 6” dia., minimum 24 MSG black or 26
MSG blue steel stove pipe to connect the stove
to the chimney. Do not use galvanized stove pipe.
Secure pipe to damper and all pipe joints with three
(3) sheet metal screws in each stove pipe and/or
elbow joint to firmly hold the pipe sections together.
DO NOT CONNECT ThIS STOvE TO ANY AIR
DISTRIBUTION OR DUCT SYSTEM.
5. R e c h e c k c l e a r a n c e s f r o m t h e s t o v e ,
connector stove pipe, and corner clearanc-
es using the illustrations in figures 5-7 and
your local building codes or fire protection
ordinances.