background image

Page 8

 

/ PB65XL

 

Vogelzang International Corp. 

VGZ-003 / 20120327.0

Fig. 11 - Chimney Construction Through Roof

Fig. 12 - Chimney Connection to Firebox  

Through Masonry Wall

CHIMNEY CONNECTIONS continued …

MANUFACTURED CHIMNEY

R E F E R  T O   C H I M N E Y   A N D   C H I M N E Y  
CONNECTOR MAKER’S INSTRUCTIONS  
FOR INSTALLATION AND USE.

Use only a 6˝ diameter manufactured chimney sys-

tem listed to UL 103 HT. Chimney made to this listing 
is High Temperature rated to 2100 degrees Fahrenheit. 
Use chimney from only one manufacturer. Never mix 
brands. Carefully follow the chimney manufacturer’s 
stated requirements and clearances. Use the chimney 
manufacturer’s attic guards, roof supports, flashing and 
fire stops when passing through a ceiling. Use a listed 

thimble when passing through a combustible wall. Do 
not use makeshift compromises during installation. 

WARNING: DO NOT USE SINGLE WALL CON-
NECTOR PIPE AS A CHIMNEY - A HOUSE FIRE 
COULD RESULT.

When using a pre-existing chimney, have it’s condi-

tion and installation inspected before using. Make sure 
that the chimney meets all of the UL rating require-
ments listed above. Be aware that not all manufactured  
chimney is of the UL 103 HT type.

NOTE: It is recommended that you contact a  

licensed heating and cooling contractor (consult your 
local yellow pages) for chimney installation.

Manufactured chimney with the proper required UL 

listing is available from most home centers, hardware 
stores, and HVAC supply stores.

If you have access to the internet, you may wish 

to view chimney manufacturers’ information on-line. 
See, www.duravent.com, www.selkirkinc.com, or www.
mtlfab.com.

VENTING TO EXISTING FIREPLACE

In some instances, people desire to convert an ex-

isting fireplace for stove use. Usually, safe connection to 
an existing masonry chimney requires more work than 
using a prefabricated chimney. The existing fireplace 
must be closed and sealed at the damper with high-
temperature caulk, ceramic wool, or furnace cement. 
Prior to installation, clean and inspect the existing flue 
and smoke shelf. Installation should be designed so 
the system can be dismantled for periodic cleaning and 
inspection. Before conversion, make sure the existing 
chimney is structurally sound, the chimney incorporates 
a flue liner and make sure it is in good condition. (A flue 
liner consists of clay tile that protects the brickwork of 
a chimney. If a chimney does not have a liner, or it is 
damaged, have it relined by a professional. 

DO NOT 

USE a chimney that is unlined or damaged!

) If you 

have any question regarding the condition of the chim-
ney, consult a qualified licensed contractor, qualified 
engineer, competent mason, certified Chimney Sweep, 
or a knowledgeable inspector. Consult your insurance 
company if you cannot find a qualified expert.

CAUTION: NOT ALL FIREPLACE CHIMNEYS 
ARE SUITABLE FOR CONVERSION TO ACCOM-
MODATE CONNECTION TO A WOOD STOVE. 
CHECK WITH A QUALIFIED EXPERT.

Many prefabricated fireplaces are of the “zero-

clearance fireplace” category. These consist of 
multi layered metal construction. They are designed 
with enough insulation and/or air cooling on the 
base, back and sides so they can be safely in-
stalled in direct contact with combustible floors and 
walls. Although many prefabricated fireplaces carry  

Continued on next page

Содержание PB65XL

Страница 1: ...S STOVE FAILURE TO FOLLOW INSTRUC TIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH THIS STOVE IS NOT A UL LISTED STOVE NOTE IT IS RECOMMENDED INSTALLATION BE COMPLETED BY A QUALIFIED HEATING EQUIPMENT INSTALLER DO NOT INSTALL IN A MOBILE HOME REFER TO MARKINGS ON STOVE LABELS FOR ADDITIONAL INFORMATION SAFETY NOTICE IF THIS STOVE IS NOT PROPERLY INSTALLED A HOUSE BUILDING FIRE MAY R...

Страница 2: ... system listed to UL 103 HT Residential Type and Building Heating Appli ance Chimney Use a 6 152mm diameter chim ney that is high enough to give a good draft See specifics in Chimney Connections instructions 11 Be sure that your chimney is safely constructed and in good repair Have the chimney inspected by the fire department or a qualified inspector Your insurance company should be able to recommend...

Страница 3: ... HEAT ING AND COOLING CONTRACTOR MUST BE CONSULTED IF YOU HAVE QUESTIONS REGARDING THE INSTALLATION OF THIS SOLID FUEL BURNING APPLIANCE 18 This stove has a painted surface which is durable but it will not stand rough handling or abuse When installing your stove use care in handling 19 Clean exterior with soap and warm water when stove is not hot Do not use any acids or scouring soap as these solv...

Страница 4: ...ht section of stove pipe fig 1 exiting the stove before the stove is used a Drill two 1 4 holes centered on either side of the pipe section 6 from the top end of the pipe figure 1 b Remove the handle from the damper then slide the damper into the pipe c Align the damper with the holes drilled in step 9a and insert the handle through the holes and the damper NOTE THIS DAMPER IS NECESSARY FORTHE PROPE...

Страница 5: ...D ADDITIONAL FLOOR PROTECTION REQUIRED BACKWALL 54 TOP VIEW 36 18 18 18 36 63 18 SIDEWALL COMBUSTIBLE CONSTRUCTION ACCORDING TO NFPA 211 COMBUSTIBLE CONSTRUCTION ACCORDING TO NFPA 211 6 152mm i d ma nu fa cured chimney system listed to UL 103 HT Maximum 64 square inches 4 Use 6 152mm diameter minimum 24 MSG Black or 26 MSG Blue round stove pipe DO NOT USE GALVANIZED duct pipe Secure pipe sections ...

Страница 6: ...e than two 2 90 degree bends be used in the stovepipe in stallation The use of more than two 90 degree bends may decrease the amount of draw and possibly cause smoke spillage Where pos sible use only corrugated nonadjustable elbows These provide a better seal 7 The connector pipe must not pass through an attic or roof space trusses closet or any concealed space or floor ceiling wall or com bustible...

Страница 7: ...e trees terrain and chimney temperature can have an adverse effect on the draft The manufacturer cannot be held responsible for external factors leading to less than optimal drafting Should you have a problem with inadequate draft you should contact a licensed heating and cooling contractor for assistance in solving the problem IMPORTANT Installation Points 1 Size chimney flue to stove collar This ...

Страница 8: ...rmation on line See www duravent com www selkirkinc com or www mtlfab com VENTING TO EXISTING FIREPLACE In some instances people desire to convert an ex isting fireplace for stove use Usually safe connection to an existing masonry chimney requires more work than using a prefabricated chimney The existing fireplace must be closed and sealed at the damper with high temperature caulk ceramic wool or fu...

Страница 9: ...sitioning the center of the stove pipe entry into the chimney 24 below the ceiling should insure proper clearance for a 6 stovepipe 2 Install a metal or fire clay 5 8 minimum thickness thimble Make sure the thimble is flush with the inner surface of the chimney liner and does not protrude into the flue see figure 8 on page 6 3 Secure the thimble with refractory mortar The thimble should be surrounded ...

Страница 10: ...s separated from combustibles by a minimum of 6 152mm of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 51mm larger than the chimney connector and having 1 25 4mm or more of insulation serving as a pass through f...

Страница 11: ... be air dried sea soned for a minimum of 6 months Logs greater than 6 in diameter should be split Wood should be stored in a dry well ventilated area The humidity content for usable firewood must be less than 20 of the weight of the log Attempts to use wet or unseasoned wood will cause ignition problems rapid creosote build up with possible chimney fire incomplete combustion low heat yield Chestnut ...

Страница 12: ...e Dispose of ashes properly See Safety Instructions 14 page 2 CHIMNEY DRAFT Draft is a function of the chim ney not the stove do not expect the stove to draw Smoke spillage into the house or excessive buildup of condensation or creosote in the chimney are warnings that the chimney is NOT functioning properly Correct the problem before using the stove Following are some possible causes for improper...

Страница 13: ...T CONTROL AND FLUE PIPE DAMPER 2 GET OUT OF THE HOUSE 3 CALL THE FIRE DEPARTMENT SOOT Formation need for Removal CAUTION RISK OF FIRE When coal is burned the products of combustion combine with moisture to form a soot residue which accumu lates in the flue lining When ignited this soot makes an extremely hot fire The chimney connector and chimney should be inspected at least once every two months du...

Страница 14: ... identify parts Contact us at 616 396 1911 to order parts Part No Description Qty 1 Cook Lid 1 2 Lid Lifter 1 3 Collar Top 1 4 Top Plate 1 5 Upper Chamber 1 6 Feed Chamber 1 7 Feed Door 1 8 Spin Draft 1 9 Spring Handle 1 10 Burn Chamber 1 11 Shaker Door 1 Part No Description Qty 12 Shaker Grate 1 13 Lower Chamber 1 14 Base 1 15 Leg 4 16 Ash Door 1 17 Slide Draft 1 18 Slide Draft Knob 1 19 Ash Draw...

Страница 15: ...protector a Use formulas in step 1 above to calculate R value of proposed material s b For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the floor protector system is equal to or greater than the floor protector specifications given the alternate is acceptable Definitions Thermal conductance C BTU W hr ft2 F m2 K Thermal conductivity k Btu inch W B...

Страница 16: ...s and must be treated with respect Stay warm and in good health Respectfully yours Proprietor Vogelzang International Corporation 400 West 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 COMPANY TESTIMONY FOR GOD SO LOVED THE WORLD THAT HE GAVE HIS ONLY BEGOTTEN SON THAT WHOEVER BELIEVES IN HIM SHALL NOT PERISH BUT HAVE ETERNAL LIFE JOHN 3 16 MADE IN CH...

Отзывы: