background image

VGZ-005 / 20120202.0

 

BX42E-SN /

 

Page 17

Vogelzang International Corp.

A. 

Brick Masonry

 

Minimum 3.5˝/ 89mm thick brick masonry all framed 
into combustible wall with a minimum of 12˝/305mm  
brick separation from clay liner to combustibles. The 
fireclay liner shall run from outer surface of brick 
wall to, but not beyond, the inner surface of chimney 
flue liner and shall be firmly cemented in place.

B. Insulated 

Sleeve

 

Solid-insulated, listed factory-built chimney length 
of the same inside diameter as the chimney con-
nector and having 1˝/25.4mm or more of insulation 
with a minimum 9˝/229mm air space between the 
outer wall of the chimney length and combustibles.

C. Ventilated 

Thimble

 

Sheet steel chimney connector, minimum 24 gauge 
in thickness, with a ventilated thimble, minimum 24 
gauge in thickness, having two 1˝/25.4mm air chan-
nels, separated from combustibles by a minimum of 
6˝/152mm of glass fiber insulation. Opening shall be 
covered, and thimble supported with a sheet steel 
support, minimum 24 gauge in thickness.

D.  Chimney Section Pass-through

 

Solid insulated, listed factory-built chimney length 
with an inside diameter 2˝/51mm larger than the 
chimney connector and having 1˝/25.4mm or 
more of insulation, serving as a  pass-through 
for a single wall sheet steel chimney connector 
of minimum 24 gauge thickness, with a minimum 
2˝/51mm air space between the outer wall of chim-
ney section and combustibles. Minimum length 
of chimney section shall be 12˝/305mm chimney 
section spaced 1˝/25.4mm away from connector 
using sheet steel support plates on both ends of 
chimney section. Opening shall be covered, and 
chimney section supported on both sides with 
sheet steel support securely fastened to wall sur-
faces of minimum 24 gauge thickness. Fasteners 
used to secure chimney section shall not penetrate  
chimney flue liner.

CHIMNEY CONNECTOR SYSTEMS & CLEARANCES

Содержание DELUXE BOXWOOD BX42E

Страница 1: ...ichigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 DELUXE BOXWOOD STOVE Model BX42E Owners Manual save this manual for future reference NOTE THIS STOVE IS NOT A UL LISTED STOVE READ ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS STOVE FAILURE TO FOLLOW INSTRUC TIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH REFER TO MARKINGS ON STOVE LABELS FOR ...

Страница 2: ...sonry or an Underwriters Laboratories Listed UL 103 HT Residential Type and Building Heating Appliance Chimney Use a 6 152mm diameter chimney that is high enough to give a good draft See specifics in Chimney Connections instructions 10 Be sure that your chimney is safely constructed and in good repair Have the chimney inspected by the fire department or a qualified inspector Your insurance company sh...

Страница 3: ...UNLESS SPECIFICALLY APPROVED FOR SUCH INSTALLATIONS 30 A WOOD BURNING STOVE MUST NEVER BE INSTALLED IN A HALLWAY OR NEAR A STAIR CASE as it may block egress in the event of a fire 31 DO NOT INSTALL IN A SLEEPING ROOM SAFETY INSTRUCTIONS continued DO NOT INSTALLTHIS UNIT IN AN ALCOVE OR INSIDE A FIREPLACE 32 Install at least one smoke detector on each floor of your home Detectors should be located aw...

Страница 4: ...erating Instructions House Fire Hazards Operating Precautions Warnings 12 Wood Types Sizes 12 Starting a Fire 12 Adding Fuel 13 Service Hints Creosote Formation Prevention Need for Removal 13 Stove Joints 14 Gasket Replacement 14 Parts Deluxe Boxwood 15 Floor Protector Calculations 16 Chimney Connection Systems Clearances 17 NOTE A PROFESSIONAL LICENSED HEAT ING AND COOLING CONTRACTOR MUST BE CONS...

Страница 5: ... Flooring Protection 52 x 74 as specified see page 3 Chimney Connection 6 black steel 24 ga min straight or elbow as required 1 2 Sheet Metal Screws Chimney Existing 6 Lined Ma sonry Chimney or 6 Inside Dia listed Type HT chimney Furnace Cement manufacturer recommends Rutland Code 78 or equivalent NOTICE Vogelzang International Corp grants no warranty stated or implied for the installation or maint...

Страница 6: ...th ods see page 16 Floor protector must extend at least 18 beyond the front of the hearth to the sides and beyond the rear of the stove The area under a horizontal run of the chimney connector must also be protected extending two 2 inched beyond the outer dimension of the horizontal connector The minimum sized floor protector for this stove is 52 x 74 Consult local building codes and fire protection...

Страница 7: ...ng codes or fire protection ordinances NOTE ANY WALL CONTAINING COMBUSTI BLEMATERIALSUCHASWOODENSTUDSOR DRYWALLANDFACEDWITHBRICKORSTONE MUST BE CONSIDERED A COMBUSTIBLE SURFACE 6 DO NOT INSTALL THIS STOVE IN A MOBILE HOME MANUFACTURED HOME TRAILER OR TENT NO EXCEPTIONS HUD Federal Stan dard 24 CFR Ch XX Figure 7 Minimum Clearance Dimensions from Combustible Surfaces 7 The clearances provided are m...

Страница 8: ...h the crimped end towards the stove This will allow any condensation in the flue to run back into the firebox 2 Horizontal pipe runs must slope upwards towards the chimney at least 1 4 6 4mm per foot of horizontal run 3 You must have at least 18 457mm of clearance between any horizontal piping and the ceiling 4 The pipe cannot extend into the chimney flue figure 9 5 Secure pipe elbow sections with th...

Страница 9: ...verse effect on the draft The manufacturer cannot be held responsible for external factors leading to less than optimal drafting Should you have a problem with inadequate draft you should contact a licensed heating and cooling con tractor for assistance in solving the problem IMPORTANT Installation Points 1 Size chimney flue to stove collar This stove requires a minimum of a 6 152mm diameter flue 2...

Страница 10: ...c com or www mtlfab com VENTING TO EXISTING FIREPLACE In some instances people desire to convert an ex isting fireplace for stove use Usually safe connection to an existing masonry chimney requires more work than using a prefabricated chimney The existing fireplace must be closed and sealed at the damper with high temperature caulk ceramic wool or furnace cement Prior to installation clean and inspe...

Страница 11: ... installer 1 An entry hole must be cut through the masonry and tile liner with minimal damage to the liner At least 8 of liner must remain below the entry position When locating the stove and stovepipe all minimum clear ances must be observed from combustible surfaces including mantels combustible trimwork ceilings and walls Positioning the center of the stove pipe entry into the chimney 24 below ...

Страница 12: ... fire is burning briskly Use care not to smother the kindling fire when adding wood Close the door and secure tightly 6 Adjust the collar draft damper and door spin draft control The more closed the spin draft is set the lower and slower the fire will burn The more open the faster and hotter the fire will burn Do not over fire the stove continued on next page CAUTION HOUSE FIRE HAZARDS s 4 34 2 7 2 02 ...

Страница 13: ...ORS OR STOVE GLOWS RED IMMEDIATELY CLOSE THE DOOR DAMPER AND SPIN DRAFTTO RE DUCETHE AIR SUPPLY AND SLOW DOWNTHE FIRE TOO MUCH WOOD OR BURNING NON RECOMMENDED MATERIALS SUCH AS TRASH OR FLAMMABLE LIQUIDS MAY CAUSE OVER FIRING continued on next page CAUTION DO NOT OVER FIRE APPLIANCE CAUTION SLOW BURNING FIRES AND EX TENDED USE MAY CAUSE EXCESSIVE CREO SOTE BUILDUP IGNITION OF CREOSOTE BUILDUP OR O...

Страница 14: ...w Smoke spillage into the house or excessive buildup of condensation or creosote in the chimney are warnings that the chimney is NOT functioning properly Correct the problem before using the stove Following are some possible causes for improper draft 1 The connector stovepipe may be pushed into the chimney too far stopping the draft 2 If the chimney temperature is too cool water will condense in t...

Страница 15: ... identify parts Contact us at 616 396 1911 to order parts Part No Description Qty 42 01 Leg 4 42 02 Bottom 1 42 03 Side 2 42 04 Back 1 42 05 Front 1 42 06 Door 1 42 07 Top 1 42 08 Damper Slide Draft 1 42 09 Lid 2 42 10 Lid Support 1 42 11 Hearth 1 42 12 Damper Collar Assembly 1 42 13 Handle Assembly 1 42 14 Lid Lifter L 1 1 42 15 42 16 S Hook used to hang lid lifter 1 42 17 Spin Draft 1 42 18 Door...

Страница 16: ...tector a Use formulas in step 1 above to calculate R value of proposed material s b For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the floor protector system is equal to or greater than the floor protector specifications given the alternate is acceptable Definitions Thermal conductance C BTU W hr ft2 F m2 K Thermal conductivity k Btu inch W Btu ...

Страница 17: ...ls separated from combustibles by a minimum of 6 152mm of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 51mm larger than the chimney connector and having 1 25 4mm or more of insulation serving as a pass through ...

Страница 18: ... be treated with respect Stay warm and in good health Respectfully yours Proprietor COMPANY TESTIMONY Vogelzang International Corporation 400 West 17th Street Holland Michigan 49423 www vogelzang com Phone 1 616 396 1911 Fax 1 616 396 1971 FOR GOD SO LOVED THE WORLD THAT HE GAVE HIS ONLY BEGOTTEN SON THAT WHOEVER BELIEVES IN HIM SHALL NOT PERISH BUT HAVE ETERNAL LIFE JOHN 3 16 MADE IN CHINA SteveV...

Отзывы: