1�- VERIFICATION UPON RECEPTION
Check the following points when you receive the device:
a) The device meets the specifications described in your order.
b) The device has not suffered any damage during transport.
c) Perform an external visual inspection of the device prior to switching it on.
d) Check that it has been delivered with the following:
- Installation guide
If any problem is noticed upon reception, immediately contact the transport
company and/or
VMC’s
after-sales service.
2�- PRODUCT DESCRIPTION
DREC-C
is a 2 or 4-pole type A RCCB linked to a smart reclosing mo tor, which enables safe
reclosing of the corresponding RCCB.
In the
DREC-C-2P
model, the insulation reclosing mode is used for high sensitivity protection,
so that the device only recloses when the fault that caused tripping has disappeared. The rest
of the models imple ment the timed reclosing mode to ensure power supply continuity.
The device features:
-
2 LED
indication.
- Automatic reclosing by insulation or Time, depending on the model (
).
-
Protection cover
for the reclosing system.
-
Mode selection
switch
to select between Manual and Automatic operating mode and
physically lock the reclosing device.
Table 3: DREC-C Models�
Models
Reclosure mode
Rated current (In)
Sensitivity (
Δ
In)
DREC-C-2P-40-30
Isolation
40 A
30 mA
DREC-C-2P-63-30
Isolation
63 A
30 mA
DREC-C-2P-40-300
Time
40 A
300 mA
DREC-C-2P-63-300
Time
63 A
300 mA
DREC-C-4P-40-30
Time
40 A
30 mA
DREC-C-4P-63-30
Time
63 A
30 mA
DREC-C-4P-40-300
Time
40 A
300 mA
DREC-C-4P-63-300
Time
63 A
300 mA
6
DREC-C
Instruction Manual