30
contact the local appointed service center and also give a description of the error occurred as well
as the model of the unit.
12.2 Problem Handling
The conditions listed below are not classified into errors.
Conditions
Causes
The unit does
not run
When restart the unit soon after it
is stopped
The overload protection switch of the unit let
the startup delayed for three minutes
As soon as power supply is on
The unit will stand by for approximate one
minute
The unit blows
out mist
When the cooling operation
starts
The hi-humidity air indoor is cooled quickly
The unit
generates
noise
The unit "clatters" as soon as it
starts running
It is the sound generated during the
initialization of the electronic expansion valve
The unit "swishes" during the
cooling operation
It is the sound when the refrigerant gas runs
inside the unit
The unit "swishes" when it is
started or stopped
It is the sound when the refrigerant gas stops
running
The unit "swishes" when it is in
and after the running
It is the sound when the draining system is
operating
The unit "squeaks" when it is in
and after the running
It is the sound of frication generated by the
skin plate etc which swells due to the
temperature change
The unit blows
out dust
When the unit restarts after it is
not used for a long time
The dust inside the unit is blown out again
The unit emits
odors
When the unit is running
The odors absorbed in are blown out
Errors of definition
Main control display for outdoor unit
Indoor unit
code
Testing board
code
Yellow LED
Red LED
Green LED
The compressor is startup
Flash 1 time
IPM current protection
Flash 3
times
H5
H5
IPM temperature protection
Flash 5
times
P8
P8
PFC current protection
Flash 7
times
HC
HC
12.3 Error Description
If some error occurs when the unit is running, the error code will be displayed on the wired
controller, the main board and the testing board of the outdoor unit. Check for more details about
the meaning of each error.
Содержание ACP-48COFM140GEEI
Страница 1: ...Upute za uporabu User manual ACP 56COFM164GEEI ACP 48COFM140GEEI RoHS 14 ...
Страница 2: ...ENG User manual RoHS 14 ACP 56COFM164GEEI ACP 48COFM140GEEI ...
Страница 13: ...8 4 2 Outline Dimension of Outdoor Unit Fig 3 mm ...
Страница 17: ...12 3 For three BU modules there will not be more than nine indoor units Fig 10 ...
Страница 42: ...HR BiH Upute za uporabu RoHS 14 ACP 56COFM164GEEI ACP 48COFM140GEEI ...
Страница 53: ...8 4 2 Nacrt dimenzija vanjske jedinice Sl 3 mm ...
Страница 57: ...12 3 Za tri BU modula gdje neće biti više od devet unutarnjih jedinica Sl 10 ...
Страница 83: ......
Страница 87: ......
Страница 93: ...3 4 ...
Страница 100: ...3 4 3 4 3 4 ...
Страница 109: ...www vivax com ...
Страница 110: ...www vivax com ...