13
The sorts
The pipes
Length
(m)
Maximum
allowable
length
Between outdoor unit and BU
L1+L2+L3+L4+L5
≤55
Between
indoor unit
and BU
ACP-48COFM140GEEI
1A+1B+1C+2A+2B+2C+
3A+3B+3C
≤80
ACP-56COFM164GEEI
≤90
Between indoor unit and BU
module
1A;1B;1C;2A;2B;2C;3A;3B;3C
≤15
Between indoor unit and the 1st
branch
L4+1B;L2+L5+2A;
L2+L3+3B
≤40
Maximum
allowable
length
Between outdoor and indoor units
H1
≤30
Between outdoor units and BU
H2
≤30
Between BU and BU modules
H3
≤15
Between indoor and indoor units
H4
≤15
Minimum
allowable
length
Between outdoor and
the 1
st
branch
L1
≥5
Between BU and the branch
L3;L4;L5
as possible
as short
Fig. 11 (9 indoor units)
Table 3
6.2
Allowable Length and Drop Height of Connecting Pipe
Fig. 11 (9 in door units)
Table 3
Содержание ACP-48COFM140GEEI
Страница 1: ...Upute za uporabu User manual ACP 56COFM164GEEI ACP 48COFM140GEEI RoHS 14 ...
Страница 2: ...ENG User manual RoHS 14 ACP 56COFM164GEEI ACP 48COFM140GEEI ...
Страница 13: ...8 4 2 Outline Dimension of Outdoor Unit Fig 3 mm ...
Страница 17: ...12 3 For three BU modules there will not be more than nine indoor units Fig 10 ...
Страница 42: ...HR BiH Upute za uporabu RoHS 14 ACP 56COFM164GEEI ACP 48COFM140GEEI ...
Страница 53: ...8 4 2 Nacrt dimenzija vanjske jedinice Sl 3 mm ...
Страница 57: ...12 3 Za tri BU modula gdje neće biti više od devet unutarnjih jedinica Sl 10 ...
Страница 83: ......
Страница 87: ......
Страница 93: ...3 4 ...
Страница 100: ...3 4 3 4 3 4 ...
Страница 109: ...www vivax com ...
Страница 110: ...www vivax com ...