Service manual
36
13. Troubleshooting
13.1
Display board
Thi s indicator illuminates whe n the air conditioner is in AUTO operation.
AU TO indicator
DE FROST indicator (F or Cooling & H eating mo dels only)
Thi s indicator illuminates whe n the air conditioner starts defrostin g automati cally or
when the warm air control fea ture is activated in he ating oper ation.
1
22
3
4 5
1
22
3
4
Displays the te mperature settings when the air conditioner is operational.
This indicator flashe s after power is on and illuminates when the unit is in operation.
This indicator il luminates when TIMER is set ON/OFF.
OPERATION in dicator
TIMER indicator
TEMPERATUR E indicator
5
Signal receptor
13.2
Troubleshooting
For models adopting electrical function
Failure phenomenon
Operation
lamp
Timer
lamp
Defrosting
lamp
Auto
lamp
Over current protection of the compressor occurs 4
times
☆
☆
☆
☆
Indoor room temp. sensor is open circuit or short
circuit
X
☆
X X
Temp. sensor on indoor evaporator is open circuit
or short circuit
☆
X X
X
Temp. sensor on outdoor condenser is open circuit
or short circuit (without for cooling only models)
X X
☆
X
Outdoor unit protects(outdoor temp sensor, phase
order etc)
X X
☆
☆
EEROM error
X
☆
X
☆
Indoor unit communication err
X
X
X
☆
r
Extinguish
☆
Flash at 5Hz
NOTE: For cool only model, the defrosting lamp is replaced with fan lamp, but malfunction display remains.
Содержание ACP-24CH70AEB
Страница 1: ...ACP 24CH70AEB RoHS Service manual ENG ...
Страница 2: ......
Страница 5: ......
Страница 14: ...Service manual 9 5 Refrigerant cycle diagram Cooling only Heat pump mode ...
Страница 18: ...Service manual 13 7 2 Wiring diagram MSE 21CRN2 MSE 24CRN2 MSE 28CRN2 ...
Страница 19: ...Service manual 14 MSE 21HRN2 ACP 24CH70AEB MSE 28HRN2 ...
Страница 48: ......
Страница 49: ......
Страница 50: ......