Troubleshooting
150
Electrical Control System
2.4.4.5. E5 malfunction
Check whether the power
voltage is normal.
Measure whether outdoor
terminal voltage is normal
?
Restart the unit when the power
supply gets normal
No
Yes
No
Reconnect it well
Yes
Yes
No
Replace the IPM board, If the IPM board
and main board is in a board, replace the
outdoor main PCB
Yes
Replace the PFC module(If has)
No
Yes
Measure whether the voltage
between L and N is normal
?
Yes
Measure whether input voltage
of bridge rectifier is normal
?
Yes
No
No
Measure whether the voltage
between P and N is normal
refer
to
the
Appendix
3
?
Replace the bridge
rectifier
No
Check whether
bridge rectifier is
normal
Check the wiring of
reactor or inductance
Reconnect the
wiring
No
Check whether reactor
or inductance is normal
Yes
Replace reactor or
inductance
No
Check the wiring of
power wires well or
correctly
Reconnect it well
Check the wiring of
L and N well or
correctly
Reconnect it well
Check the wiring of
bridge rectifier well
or correctly
E5 display
Voltage protection of compressor
Содержание ACP-12CC35AECI
Страница 2: ......
Страница 4: ......
Страница 15: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 18: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Страница 19: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55K Cooling Heating ...
Страница 24: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Страница 31: ...Wiring Diagrams 28 Indoor Units 4 Wiring Diagrams MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0 ...
Страница 33: ...Static Pressure 30 Indoor Units 5 Static Pressure MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0 ...
Страница 34: ...Static Pressure Indoor Units 31 MTB 24HWFN1 QRD0 MTB 30HWFN1 QRD0 ...
Страница 35: ...Static Pressure 32 Indoor Units MTB 36HWFN1 QRD0 MTB 42HWFN1 QRD0 MTB 48HWFN1 QRD0 MTB 55HWFN1 QRD0 ...
Страница 44: ...Service Space Indoor Units 41 3 Service Space ...
Страница 46: ...Wiring Diagrams Indoor Units 43 Pre setting Instructions ...
Страница 55: ...52 Indoor Units 10 Field Wiring ...
Страница 59: ...Service Space 56 Indoor Units 3 Service Space ...
Страница 60: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AECI ACP 18CC50AECI ...
Страница 64: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AECI ACP 18CC50AECI ...
Страница 68: ...Dimensions Console Type 65 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 69: ...Service Space 66 Console Type 3 Service Space ...
Страница 70: ...Wiring Diagrams Console Type 67 4 Wiring Diagrams MFAU 12HRFN1 QRD0W ...
Страница 75: ...Field Wiring 72 Console Type 10 Field Wiring MFAU 12HRFN1 QRD0W ...
Страница 81: ...Wiring Diagrams 78 Outdoor Units 4 Wiring Diagrams MOZU 12HFN1 QRD0W MOZU 18HFN1 QRD0 ...
Страница 82: ...Wiring Diagrams Outdoor Units 79 MOFU 24HFN1 QRD0 MOYU 30HFN1 QRD0 ...
Страница 83: ...Wiring Diagrams 80 Outdoor Units MOYU 36HFN1 QRD0 ...
Страница 84: ...Wiring Diagrams Outdoor Units 81 MOYU 36HFN1 RRD0 MOYU 42HFN1 RRD0 ...
Страница 85: ...Wiring Diagrams 82 Outdoor Units MOEU 48HFN1 QRD0 MOEU 48HFN1 R MOEU 55HFN1 RRD0RD0 ...
Страница 111: ...Refrigerant pipe installation 108 Installation ...
Страница 149: ...Troubleshooting 146 Electrical Control System 2 4 4 2 E2 malfunction For current loop communication ...
Страница 151: ...Troubleshooting 148 Electrical Control System 2 4 4 3 E3 malfunction ...
Страница 154: ...Troubleshooting Electrical Control System 151 2 4 4 6 E8 malfunction The same as E8 in indoor 2 4 4 7 P0 malfunction ...
Страница 155: ...Troubleshooting 152 Electrical Control System 2 4 4 8 P1 malfunction For 36k models ...
Страница 161: ...Troubleshooting 158 Electrical Control System 2 4 4 14 P7 malfunction ...
Страница 174: ...www VIVAX com ...