Electrical Control Function
130
Electrical Control System
1.3.5 Drying mode
For 12K models:
Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in cooling mode.
Low indoor room temperature protection
In drying mode, if room temperature is lower than 10
℃
, the compressor will stop and not resume until room
temperature exceeds 12
℃
.
All protections are active and the same as that in cooling mode.
For other models: Drying mode works the same as cooling mode in low speed.
All protections are active and the same as that in cooling mode.
1.3.6 Timer function
1.3.6.1 Timing range is 24 hours.
1.3.6.2 Timer on. The machine will turn on automatically when reaching the setting time.
1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time.
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
1.3.6.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not
start up firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be
off and the AC running mode has not been changed.
1.3.6.7 The setting time is relative time.
1.3.7 Economy function
1.3.7.1 The sleep function is available in cooling, heating or auto mode.
1.3.7.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed.
When heating, the setting temperature decreases 1
℃
(be higher than 17
℃
) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode but doesn’t turns off,
but for console, the unit will turn off.
1.3.7.4 Timer setting is available
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including economy function and
auxiliary functions
)
automatically after 3 minutes when power returns.
Содержание ACP-12CC35AECI
Страница 2: ......
Страница 4: ......
Страница 15: ...Service Space 12 Indoor Units 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Страница 18: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating ...
Страница 19: ...Air Velocity Distributions Reference Data 16 Indoor Units 48 55K Cooling Heating ...
Страница 24: ...Field Wiring Indoor Units 21 10 Field Wiring ...
Страница 31: ...Wiring Diagrams 28 Indoor Units 4 Wiring Diagrams MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0 ...
Страница 33: ...Static Pressure 30 Indoor Units 5 Static Pressure MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0 ...
Страница 34: ...Static Pressure Indoor Units 31 MTB 24HWFN1 QRD0 MTB 30HWFN1 QRD0 ...
Страница 35: ...Static Pressure 32 Indoor Units MTB 36HWFN1 QRD0 MTB 42HWFN1 QRD0 MTB 48HWFN1 QRD0 MTB 55HWFN1 QRD0 ...
Страница 44: ...Service Space Indoor Units 41 3 Service Space ...
Страница 46: ...Wiring Diagrams Indoor Units 43 Pre setting Instructions ...
Страница 55: ...52 Indoor Units 10 Field Wiring ...
Страница 59: ...Service Space 56 Indoor Units 3 Service Space ...
Страница 60: ...Wiring Diagrams Indoor Units 57 4 Wiring Diagrams ACP 12CC35AECI ACP 18CC50AECI ...
Страница 64: ...Field Wiring Indoor Units 61 10 Field Wiring ACP 12CC35AECI ACP 18CC50AECI ...
Страница 68: ...Dimensions Console Type 65 2 Dimensions 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 69: ...Service Space 66 Console Type 3 Service Space ...
Страница 70: ...Wiring Diagrams Console Type 67 4 Wiring Diagrams MFAU 12HRFN1 QRD0W ...
Страница 75: ...Field Wiring 72 Console Type 10 Field Wiring MFAU 12HRFN1 QRD0W ...
Страница 81: ...Wiring Diagrams 78 Outdoor Units 4 Wiring Diagrams MOZU 12HFN1 QRD0W MOZU 18HFN1 QRD0 ...
Страница 82: ...Wiring Diagrams Outdoor Units 79 MOFU 24HFN1 QRD0 MOYU 30HFN1 QRD0 ...
Страница 83: ...Wiring Diagrams 80 Outdoor Units MOYU 36HFN1 QRD0 ...
Страница 84: ...Wiring Diagrams Outdoor Units 81 MOYU 36HFN1 RRD0 MOYU 42HFN1 RRD0 ...
Страница 85: ...Wiring Diagrams 82 Outdoor Units MOEU 48HFN1 QRD0 MOEU 48HFN1 R MOEU 55HFN1 RRD0RD0 ...
Страница 111: ...Refrigerant pipe installation 108 Installation ...
Страница 149: ...Troubleshooting 146 Electrical Control System 2 4 4 2 E2 malfunction For current loop communication ...
Страница 151: ...Troubleshooting 148 Electrical Control System 2 4 4 3 E3 malfunction ...
Страница 154: ...Troubleshooting Electrical Control System 151 2 4 4 6 E8 malfunction The same as E8 in indoor 2 4 4 7 P0 malfunction ...
Страница 155: ...Troubleshooting 152 Electrical Control System 2 4 4 8 P1 malfunction For 36k models ...
Страница 161: ...Troubleshooting 158 Electrical Control System 2 4 4 14 P7 malfunction ...
Страница 174: ...www VIVAX com ...