background image

8

 

Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.

 

Modules

 

VITM4

-

S

-

2CH

 

4 pole starter box, 2 channel

 

VITM4

-

E

-

2CH

 

4 pole extender box, 2 channel

 

Presence / Absence Detectors

 

Connectors

 

Detector Leads (LSF)

 

VITM4

-

L3

-

2CH

 

 

3m  2 channel sensor lead

 

VITM4

-

LD3

-

2CH

 

 

3m  2 channel dual detector sensor lead

 

VITM4

-

LPW

 

 

4 pole luminaire plug white

 

Luminaire Leads (LSF)

 

VITM4L303100W

 

3 core

 

3m

 

1.0mm

2

 White plug

  

VITM4L305100W

 

 

3 core   

 

5m

 

1.0mm

2

 White plug

  

VITM4L403100R

 

 

4 core

 

3m

 

1.0mm

2

 Red plug

 

VITM4L405100R

 

 

4 core

 

5m

 

1.0mm

2

 Red plug

 

Other leads available to order.

 

Part numbers

 

C.P. Electronics Ltd

 

Brent Crescent

 

London

 

NW10 7XR

 

United Kingdom

 

Tel:

 

+ 44 (0) 333 900 0671

 

Fax:

 

+ 44 (0) 333 900 0674

 

www.cpelectronics.co.uk

 

[email protected]

 

Ratings

 

Voltage

 

 

/

-

 10% 

 

Frequency

   

50Hz

 

Terminal capacity

 

4mm

2

 in wiring compartment

 

Temperature

 

0ºC to 35ºC 

 

Power

 

Rating of system 16A. Rating of each output 10A (but limited on 

the detector output rating, check datasheet of detector!

 

Compliance

  

LVD

-

2014/35/EU

 

For further compliance information visit

 

www.cpelectronics.co.uk/compliance

 

 

For lighting purposes only with suitable circuit protection. For fixed wiring 

only

 

Ref: #WD325 Issue 8

 

IMPORTANT NOTICE!

 

This device should be installed by a 

qualified electrician in accordance with 

the latest edition of the IEE wiring 

regulations.

 

UK Patent no. GB2463063

 

EU patent pending

 

EU registered design no.

 

001587544

-

0001, 001587544

-

0002

 

EBDSPIR

-

PRM

-

2CH

 

PIR 2

-

Channel presence detector

 

EBDSPIR

-

PRM

-

2CH

-

NC

 

PIR 2

-

Channel presence detector, 

 

normally closed fail safe contacts

 

MWS3A

-

PRM

-

2CH

 

Microwave 2

-

Channel presence detector

 

MWS3A

-

PRM

-

2CH

-

NC

 

Microwave 2

-

Channel presence detector, normally closed fail safe contacts

 

MWS6

-

PRM

-

2CH

 

Microwave 2

-

Channel presence detector

   

MWS6

-

PRM

-

2CH

-

NC

 

Microwave 2

-

Channel presence detector, normally closed fail safe contacts

 

 

Содержание VITM4-2CH

Страница 1: ...r starter for non dimming systems VITM4 E 2CH Vitesse modular extender for non dimming systems Channel for channel nuts zebs Removable gland plate with 3 x Ø20mm knockouts 3 x Ø20mm knockouts for rear cable entry 4 x key slots to accept M6 1 4 fixings BESA box fixings 202mm 150mm 146mm 127mm 122mm 75mm Fixing points M6 1 4 Warning This device works at mains voltage Be sure to take care when workin...

Страница 2: ...clamps Permanent Live Neutral Supply in Earth Live 1 Switched Live 2 Switched On Off 1 On Off 2 Live 1 Supply in Live 2 Supply in Local lighting switch and local emergency test switch N E L Local emergency test switch Local lighting switch 1 Emergency test using central switch N E L Multiple boxes DO NOT WIRE ACROSS PHASES Central emergency test switch A local lighting switch may still be used whe...

Страница 3: ...r is used to interrupt the power N E Wire link Sensor Detector lead needs to be ordered separately from the detector Order code VITM4 L3 2CH Where two detectors connect to a single box a dual lead is available VITM4 LD3 2CH CH1 and CH2 plugs are coded Ensure that the plugs are inserted correctly and do not apply excessive force L2 L1 L2 L2 L1 Central emergency test switch Local emergency test swit...

Страница 4: ...ches mode as shown short push turns ON Long held push turns OFF 1 sec Allow a few minutes initial power on setup to take place before operation the switches See detector programming manual further information Presence detector connections Automatic on automatic off Absence detector connections Manual on automatic off Switch Noise Filtering Due to the noise filtering process there is a small delay ...

Страница 5: ... luminaires are typically situated nearest the windows The luminaires will also switch with occupancy Channel 2 occupancy only The inner luminaires ie those furthest from the windows are switched with occupancy only Switch inputs One or two manual switches ie for luminaires on channels 1 and 2 can be used to manually override the lights on or off or in the case of absence detection activate the lu...

Страница 6: ...6 This page intentionally left blank ...

Страница 7: ...7 This page intentionally left blank ...

Страница 8: ... 50Hz Terminal capacity 4mm2 in wiring compartment Temperature 0ºC to 35ºC Power Rating of system 16A Rating of each output 10A but limited on the detector output rating check datasheet of detector Compliance LVD 2014 35 EU For further compliance information visit www cpelectronics co uk compliance For lighting purposes only with suitable circuit protection For fixed wiring only Ref WD325 Issue 8 ...