D-303471 TMD-560 PG2 Installation Instructions 

3

 

 

 

Define whether or not the control panel will report a "cold" alert when the temperature drops below 19

C (66

F) for 

at least 10 minutes. Alert restore will occur when the temperature rises above 20

C (68

F) for the duration of 10 

minutes. 

Options: 

 Disabled

 (default) or 

Enabled

 

 

Define whether or not the control panel will report a "freezing" alert when the temperature drops below 7

C (45

F) 

for at least 10 minutes. Alert restore will occur when the temperature rises above 8

C (48

F) for the duration of 10 

minutes. 

Options: 

 Disabled

 (default) or 

Enabled

 

 

Define whether or not the control panel will report a "freezer" alert when the temperature rises above -10

C (14

F) 

for at least 30 minutes. Alert restore will occur when the temperature drops below -11

C (12

F) for the duration of 

10 minutes. 

Options: 

 Disabled

 (default) or 

Enabled

Note: 

The temperature must pass beyond the threshold for the required duration in order to generate an alarm or restore transmission. 

2.4. Temperature Display 

For instructions on displaying the temperature of zones on the control panel as measured by TMD-560 detectors, refer to the PowerMaster 
Installer Guide, section 4.2 "Conducting a Periodic Test". 

 

3. LOCAL DIAGNOSTICS TEST 

Before testing, separate the base from the cover (see Figure 2). 

A.

  Press the tamper switch once and release it.

 

 

B. 

After 2 seconds the LED blinks 3 times.  
The following table indicates received signal strength indication. 

LED response 

Reception  

Green LED blinks 

Strong  

Orange LED blinks 

Good  

Red LED blinks 

Poor  

No blinks 

No communication 

C.

  Put back the cover to return the tamper switch to its normal (undisturbed) position, and then secure the front cover to the base with the case 

closure screw. 

IMPORTANT!

 Reliable reception must be assured. Therefore, "poor" signal strength is not acceptable. If you receive a "poor" signal from the 

device, re-locate it and re-test until a "good" or "strong" signal strength is received.

 

Note:

 Since the cover is removed and power is applied, a tamper situation exists. Verify that the TMD-560 PG2 transmits (the LED lights briefly).  

When you are satisfied that tamper alert is transmitted properly,

 

close the TMD-560 PG2 front cover on to return the tamper switch to its normal 

position. Then, secure the front cover to the base with the case closure screw. 

1.

 For detailed Diagnostics Test instructions refer to the control panel Installer Guide. 

2. 

For UL/CUL installations, the test result must be “Strong”. 

 

4. SPECIFICATIONS 

Frequency Band (MHz)

 

Europe and rest of world:

433-434, 868-869 

USA:

912-919

 

Communication Protocol

 PowerG

RFI protection 

>20 V/m 80 to 2000 MHz

Temperature measurement accuracy 

(internal sensor or optional probe) 

±

1.5

C (±2.7

F)

Probe cable length 

3.5m

 

Battery type 

3 V Lithium battery, CR123, Panasonic, Sanyo or GP only 

Battery Life Expectancy

 7 

years (for typical use)

Low Battery Threshold 

2.2 V 

Battery Supervision 

Automatic transmission of battery conditions data as part of any status report

Operating Temperature (indoor) 

-20° to 50°C (-4°F to 122°F)

Note:

 For UL installations, the ambient temperature is 32°F to 120°F (0°C to 49°C)

Probe Operating Temperature (outdoor)

 

-30° to 70°C (-22°F to 158°F)

Storage Temperature (indoor) 

-20°C to 60°C (-4°F to 140F)

Dimensions (LxWxD)

 

92 x 36.5 x 31 mm (3-5/8 x 1-7/16 x 1-1/4 in.).

Weight (excluding battery)

 

50 g (1.8 oz.).

 

FREEZER >–10ºC

 

FREEZING <7ºC

  

COLD < 19

C

 