D-303471 TMD-560 PG2 Installation Instructions
3
Define whether or not the control panel will report a "cold" alert when the temperature drops below 19
C (66
F) for
at least 10 minutes. Alert restore will occur when the temperature rises above 20
C (68
F) for the duration of 10
minutes.
Options:
Disabled
(default) or
Enabled
.
Define whether or not the control panel will report a "freezing" alert when the temperature drops below 7
C (45
F)
for at least 10 minutes. Alert restore will occur when the temperature rises above 8
C (48
F) for the duration of 10
minutes.
Options:
Disabled
(default) or
Enabled
.
Define whether or not the control panel will report a "freezer" alert when the temperature rises above -10
C (14
F)
for at least 30 minutes. Alert restore will occur when the temperature drops below -11
C (12
F) for the duration of
10 minutes.
Options:
Disabled
(default) or
Enabled
.
Note:
The temperature must pass beyond the threshold for the required duration in order to generate an alarm or restore transmission.
2.4. Temperature Display
For instructions on displaying the temperature of zones on the control panel as measured by TMD-560 detectors, refer to the PowerMaster
Installer Guide, section 4.2 "Conducting a Periodic Test".
3. LOCAL DIAGNOSTICS TEST
Before testing, separate the base from the cover (see Figure 2).
A.
Press the tamper switch once and release it.
B.
After 2 seconds the LED blinks 3 times.
The following table indicates received signal strength indication.
LED response
Reception
Green LED blinks
Strong
Orange LED blinks
Good
Red LED blinks
Poor
No blinks
No communication
C.
Put back the cover to return the tamper switch to its normal (undisturbed) position, and then secure the front cover to the base with the case
closure screw.
IMPORTANT!
Reliable reception must be assured. Therefore, "poor" signal strength is not acceptable. If you receive a "poor" signal from the
device, re-locate it and re-test until a "good" or "strong" signal strength is received.
Note:
Since the cover is removed and power is applied, a tamper situation exists. Verify that the TMD-560 PG2 transmits (the LED lights briefly).
When you are satisfied that tamper alert is transmitted properly,
close the TMD-560 PG2 front cover on to return the tamper switch to its normal
position. Then, secure the front cover to the base with the case closure screw.
1.
For detailed Diagnostics Test instructions refer to the control panel Installer Guide.
2.
For UL/CUL installations, the test result must be “Strong”.
4. SPECIFICATIONS
Frequency Band (MHz)
Europe and rest of world:
433-434, 868-869
USA:
912-919
Communication Protocol
PowerG
RFI protection
>20 V/m 80 to 2000 MHz
Temperature measurement accuracy
(internal sensor or optional probe)
±
1.5
C (±2.7
F)
Probe cable length
3.5m
Battery type
3 V Lithium battery, CR123, Panasonic, Sanyo or GP only
Battery Life Expectancy
7
years (for typical use)
Low Battery Threshold
2.2 V
Battery Supervision
Automatic transmission of battery conditions data as part of any status report
Operating Temperature (indoor)
-20° to 50°C (-4°F to 122°F)
Note:
For UL installations, the ambient temperature is 32°F to 120°F (0°C to 49°C)
Probe Operating Temperature (outdoor)
-30° to 70°C (-22°F to 158°F)
Storage Temperature (indoor)
-20°C to 60°C (-4°F to 140F)
Dimensions (LxWxD)
92 x 36.5 x 31 mm (3-5/8 x 1-7/16 x 1-1/4 in.).
Weight (excluding battery)
50 g (1.8 oz.).
FREEZER >–10ºC
FREEZING <7ºC
COLD < 19
C