background image

D-305551 MCT-442 Installation Instructions 

3. PREPARATIONS 

3.1 Disassembly 

BRACKET

DETECTOR

1

Hold the

bracket with

one hand

2

Rotate the
detector as
shown and
pull it from
the bracket

 

Figure 2.

 Separating the Detector from Its Bracket 

3.2 Communication Format Selection 

Select the desired communication format, EN or UL,  by switch 1  (see 
figure 3). 

Note:

 Switch 2 is not used. 

3.3 Enrolling the Detector ID 

Insert battery (see figure 3). 

Battery cover

Function selector:
Sw. 1 ON = UL
Sw. 1 OFF = EN

9 volts

Open  battery  cover  and
connect  the  battery  to  its
terminals (without insulator).
Ve ri f y  pr op e r   p ol ar i t y.

Tamper switch

actuator

Tab (1 of 4)

Red button

 

Figure 3.

 Detector Rear Side

 

The ID of the detector's transmitter must be enrolled in the alarm control 
panel  memory.  Refer  to  the  alarm  control  panel’s  installation 
instructions and follow the procedure given there for enrolling detector's 
transmitter ID in the control panel's memory.  
When you are required to initiate a transmission for enrollment,  press 
the tamper switch (see fig. 3). 

Note:

  It  is  much  easier  to  carry  out  this  operation  while  holding  the 

detector in your hand, close to the control panel.

 

 

4. INSTALLATION 

4.1 Mounting 

The detector can be mounted on a wall or ceiling. For EN approved 
sites, only ceiling installation is allowed. 
It must be mounted with its bracket (when it is attached to its bracket 
the  tamper  switch  is  pressed  and  the  detector  automatic  reset  is 
performed). 

!

 Warnings 

 

Installation  must  be  performed  by  a  qualified  individual.  Failure  to 
properly  install,  test  and  maintain  a  CO  detector  may  cause  it  to 
fail, resulting in loss of life! 

 

Installation of the CO detector should not be used as a substitute for 
proper  installation,  use  and  maintenance  of  fuel  burning  appliances, 
including appropriate ventilation and exhaust systems. 

 

Unauthorized  removal  of  the  unit  from  the  bracket  will  initiate  a 
tamper alert! 

!

  Warning  - 

The  battery  must  be  inserted  into  the 

detector otherwise you will not be able to close the detector. 

4.2 Test 

A. Local Test

 

Press  the  test  button  (see  fig.  1)  until  the  built-in  buzzer  sounds  1 
beep  and  the  red,  green  and  yellow  LEDs  flash  sequentially  (see 
section  2  -  SPECIFICATION).  This  means  that  the  local  test  is 
successful.  If  additional  or  other  signals  exist,  refer  to  section  2  - 
SPECIFICATION. 

!

 

WARNING:

 The test switch is the only proper way to test the CO 

detector. Never use vehicle exhaust! Exhaust may cause permanent 
damage and void your warranty. 

B. Communication Test 

Create  a  tamper  alarm  at  the  installation  location  and  verify  that 
tamper message is received by the control panel / receiver. 

1

Locate the bracket on
mounting surface so
that the word “UP” is
located as shown (so
that the detectors
stickers text will be
easily readable)

Mark and drill 2 holes in
mounting surface. Fasten
the bracket to the mounting
surface with 2 screws.

Align detector’s tabs (see figure 3) with the bracket
slots and rotate the detector as shown. Pull the
detector outward to verify that it is securely attached.

2

3

UP

 

Figure 4. 

Mounting

 

  

5. MAINTENANCE 

!

  Warning: 

Press  the  detector's  TEST  button  once  every 

week to ensure proper operation of the detector. 

When  low  battery  alarm  exists  (see  specifications)  immediately 
replace the battery (see figure 3). 
Once  a  month,  use  vacuum  cleaner  to  clean  the  air  vents 
occasionally, to keep them free of dust. 

 

APPENDICES 

Appendix A - CO Detector Installation Overview 

A-1. Selecting Installation Location 

Selecting  a  suitable  location  is  critical  for  the  CO  detector.  The 
Consumer  Product  Safety  Commission  (CPSC)  recommends  to  use 
at least one CO detector per household, located near as possible to 
sleeping  area  of  the  home,  because  the  human  body  is  most 
vulnerable to the CO gas effect during sleeping hours.  
For  added  protection,  install  additional  CO  detector  in  every  separate 
bedroom  and  on  every  level  of  your  home.  If  your  bedroom  hallway  is 
longer than 14 meters (40 feet), install a CO detector at BOTH ends of the 
hallway.  Install  an  additional  detector  6  meters  (20  feet)  away  from  the 
furnace or fuel burning heat source.   
 

For 

maximum 

protection, 

the 

detector  should  be 
also 

located 

outside 

primary 

sleeping  areas  or 
at  each  level  of 
your  home.  Mount 
the  detector  on  a 
firm  wall  or  ceiling 
(see par. 4.1).

 

BEDROOM

BEDROOM

BEDROOM

LIVING
ROOM

KITCHEN

BASEMENT

GARAGE

CO DETECTOR

 

Figure 5. 

CO Detectors locations in a Multi-

Floor Residence

 

Содержание MCT-442

Страница 1: ... 30 ppm for 120 minutes 50 ppm for 60 minutes 100 ppm for 10 minutes Warning at 50 ppm between 60 90 minutes 100 ppm for 10 40 minutes 150 ppm within 3 minutes DIP switch in UL Mode No warning at 30 ppm for 30 days 70 ppm for 60 minutes 150 ppm for 10 minutes 400 ppm for 4 minutes Warning at 70 ppm between 60 240 minutes 150 ppm for 10 50 minutes 400 ppm between 4 15 minutes Audible Alarm Volume 8...

Страница 2: ...r sounds 1 beep and the red green and yellow LEDs flash sequentially see section 2 SPECIFICATION This means that the local test is successful If additional or other signals exist refer to section 2 SPECIFICATION WARNING The test switch is the only proper way to test the CO detector Never use vehicle exhaust Exhaust may cause permanent damage and void your warranty B Communication Test Create a tam...

Страница 3: ...hile victims are aware they are not well they become so disordered they are unable to save themselves by either exiting the building or calling for assistance Young children and household pets are typically first affected B 2 Chronic Effects on High Risk Group Individuals with coronary artery disease exposed to low levels of CO showed reduced ability to exercise The time of onset of exercise induc...

Страница 4: ...vice to an outlet on a circuit different from the one which supplies power to the receiver Consult the dealer or an experienced radio TV technician WARRANTY Visonic Limited the Manufacturer warrants this product only the Product to the original purchaser only the Purchaser against defective workmanship and materials under normal use of the Product for a period of twelve 12 months from the date of ...

Отзывы: