Technical Specifications
MODELS
Apparent power [kVA]
10
15
20
30
40
60
80
100
120
160
200
250
300
ENVIRONMENTAL
Storage temperature range
[°C]
-25 to +55 (15 - 40 recommended for longer battery life)
Operating temperature
range [°C]
0 to +40 (20 - 25 recommended for longer battery life)
Relative humidity range
% 0 - % 95 (non condensing)
Max. altitude without
derating [m]
1000
Protection level
IP 20
Maximum
power
dissipation
[W]
800
960
1280
1920
2560
3840
5120
6400
7680
10240
12800
16000
20000
[Btu]
2730
3277
4369
6553
8737
13106
17475
21843
26212
34950
43686
54607
68240
[kcal/h]
688
825
1100
1650
2200
3302
4403
5503
6604
8805
14675
18343
22899
ELECTRICAL
Mains Input
Number of phases
3P+N+PE
Nominal voltage [V]
380 / 400 / 415 (line-line)
Voltage
range for
normal
operation
(line to
neutral) [V]
Lower limit
(depends
on the load
level)
187 @ %100 load ( line- neutral )
120 @ %64 load ( line- neutral )
80V@ %42 load ( line- neutral )
-
Upper limit
280
Nominal frequency [Hz]
50 / 60
Frequency range [Hz]
+/-10%
Nominal
current [A]
wave form
sinusoidal
rms value
*(2)
13
20
26
40
53
79
105
131
158
211
263
329
395
Maximum
current [A]
wave form
Sinusoidal
rms value
17
23
30
47
61
95
125
158
195
260
325
400
488
OUTPUT @ 3PH OUTPUT UPS’S
Performance classification
according to IEC 62040-3
VFI-SS-111
Number of phases
3P+N+PE
Nominal voltage [V]
380 / 400 / 415 (line-line)
Static voltage
regulation
normal
<%1
@ %100 linear
load
battery
Nominal frequency [Hz]
50 / 60
Free running frequency
[Hz]
± % 0.01
Voltage THD @ rated
linear load
<%3
Nominal apparent power
[kVA]
10
15
20
30
40
60
80
100
120
160
200
250
300
Maximum load p. f.
0.8
Nominal active power [kW]
8
12
16
24
32
48
64
80
96
128
160
200
240
Nominal current [A] at
380V
15.2
22.7
30.3
45.5
60.6
91
121
151
181
241
302
379
453
Load crest factor @ rated
power
3:1
Overload duration
>1min @ %150 load
Efficiency (normal
operation) @rated linear
load with 0.8 PF
Up to 94% *
OUTPUT @ 1PH OUTPUT UPS’S