Page.12
*According local building regulations
Dimensions
Terminal position
Distance
mm
A
Distance to ventilation openings
Local*
B
Distance to ventilation openings
Local*
C
Distance to ventilation openings
Local*
D
Below a gutter soil pipes or drain pipes
500
E
Below eaves
500
F
Below carport, roof or balcony
From Inner and outer corners
500
G
From a vertical soil pipes or drain pipes
300
H
Inside and outside of a corner
500
I
Above an outside gas pressure regulator
1000
side of a gas pressure regulator
500
J
From a surface/boundary to a terminal
Local*
K
From a terminal facing a terminal
1000
L
From the centre of two roof terminals
450
M
Two Wall terminals above each other
1000
N
Two Wall terminals next each other
1000
9. TERMINAL POSITIONS AND CORRECT FUNCTIONING
Содержание Quadro 46
Страница 1: ...INSTALLATION INSTRUCTIONS FOR MODELS TL46 ...
Страница 33: ...Pag 1 FRANCE FR INSTRUCTIONS DE D INSTALLATION Trimline assortiment Trimline Quadro 46 1090 ...
Страница 44: ...Pag 12 9 POSITION FINALE ET FONCTIONNEMENT CORRECT Limite Seulement pour Conduit externe allongé ...
Страница 48: ...Page 1 DANSK DK INSTALLATIONSVEJLEDNING Trimline sortiment Trimline Quadro 46 1090 ...
Страница 59: ...Page 12 9 KORREKT PLACERING AF TERMINALER OG FUNKTION ...
Страница 63: ...Pág 1 ESPAÑA ES INSTRUCCIONES DE INSTALACIÓN Trimline Surtido Trimline Quadro 46 1090 ...
Страница 78: ...Pag 1 APPENDIX 1 DIMENSIONAL DRAWINGS ...
Страница 79: ...Pag 2 APPENDIX 2 INSTALLATION EXAMPLES A B C C 3 1 2 3 MAX 1000 ...
Страница 82: ...Pag 5 APPENDIX 5 PREPARATION AND INSTALLATION 3 2 1 2 1 4 3 5 ...
Страница 83: ...Pag 6 3 5 4 GAS CASSETTE 1 GAS VALVE BURNER CONTROL 2 APPENDIX 6 INSTALLING GASCONTROL GV60 ...
Страница 84: ...Pag 7 8 7 6 POSITIE WAAKVLAM BRANDER ...
Страница 85: ...Pag 8 APPENDIX 7 FITTING LOG SET ...
Страница 86: ...Pag 9 ...