![Vision.net 63060CM Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/vision-net/63060cm/63060cm_installation-manual_1032220013.webp)
Vision.net Photocell Daylighting Sensor
Installation & Operation Guide
11
TROUBLESHOOTING GUIDE
Symptom
Cause
Correction
Lights do not come on either
manually or automatically.
Lamp(s) are burned out
or missing.
Replace lamp(s) in fixture(s).
Circuit breaker is off.
Turn on circuit breaker.
Wire connections are
faulty.
Recheck all wire connections. Important!
Turn off circuit breaker before servicing.
Lights are too bright or not
bright enough.
Ambient light level(s) is/
are not set correctly.
Readjust Preset 1 (adjusts Maximum
Lamp Level) and/or Preset 2 (adjusts
Minimum Lamp Level).
or
Recapture the Low Sunlight and High
Sunlight Levels.
See “Programming: Photocell Daylight-
ing Sensor”.
Controlled lights react too
quickly to ambient light
changes.
Response Time not set
properly.
Reprogram Response Time to a higher
time setting.
The wrong fixtures react to the
light levels.
Improper relays or dim-
mers are assigned to
react to daylight har-
vesting control.
Reprogram to control the proper relays
or dimmers.
Photocell Daylighting Sensor
is not reacting to sun light
level changes.
Unit is not properly pro-
grammed.
Verify programming and reprogram as
desired.
Unit is not located in the
proper position to see
sunlight changes.
Relocate daylighting sensor to view
ambient (sunlight).
Photocell Daylighting Sensor
is not reacting to programming
IR remote control.
Batteries are expired in
IR remote.
Replace batteries.