Bit-6 is used to match the video impendance, which have to be set to on if the monitor is in the
end of the bus, otherwise set to off.
Bit-1 to Bit-5 are used to User Code setting.The DT596(F)/ID responds to 0~15 .
•Up to 1000 user cards can be registered by the door station.
•Easy management with LED status and sound hints.
•There are two master cards, one
MASTER CARD ADD
card and one
MASTER
CARD DELETE
card, When registered new master cards, the old master
cards are invalid automatically.
•Card reading distance is from 3 to 5 cm.
•The master cards are necessary when you add or delete user cards. Please
keep it well for future use.
Introduction:
6. ID Card Registration
www.viscoo.eu
Electric Lock Connection
Door Lock Controlled with Internal Power
Note:
1. Electronic lock of Power-on-to-unlock type should be used.
2. The door lock is limited to 12V, and holding current must be less than 250mA.
3. The door lock control is not timed from Exit Button(EB).
4. The
Unlock Mode
Parameter of Monitor must be set to 0 (by default). EB*
Door Lock Controlled with Dry Contact
Note:
1. The external power supply must be used according to the lock.
2. The inside relay contact is restricted to AC or DC 24V/1A.
3. The jumper must be taken off before connecting.
4. Setup the
Unlock Mode
of Monitor for different lock types.
• Power-on-to-unlock type: Unlock Mode=0 (by default)
• Power-off-to-unlock type: Unlock Mode=1