Maintenance
8
4.1 Replacing UV Lamp
Lamp replacement is a quick and simple procedure requiring no special tools. The UV lamp must be replaced after 9000
hours of continuous operation (approximately one year) in order to ensure adequate disinfection.
Procedure:
N O T I C E
Do not use water during replacement of UV lamp.
1
•
Shut off the water line to UV
chamber and release system
pressure before servicing.
2
0
30
15
45
10 mins
•
Disconnect main power
source and allow the unit to
cool for 10 minutes.
3
1
2
•
Remove the lamp connector
by squeezing the plastic
locking tabs on the side of the
connector.
4
Hg
UV
•
Remove the UV lamp in
upward direction from the
chamber and lamp connector
base.
•
Hold the UV lamp at the
ceramic ends.
5
Hg
UV
1
2
•
Insert the new lamp fully into
the chamber leaving about
two inches of the lamp
protruding from the chamber.
6
•
Attach the connector to the
UV lamp and note that the
connector will only allow
correct installation in one
position.
7
1
2
click
•
Push the lamp connector
against lamp connector base
together until an audible click
is heard.
•
Re-pressurize the system to
check for leaks.