Manual VIPA TM-E
Chapter 3
Deployment TM-E
HB39E - TME - RE_900-1E660 - Rev. 09/11
3-43
For example you may monitor the following values of your VIPA PLC:
DB 1, Byte 13, Bit 3
•
For this open the Web page of the TM-E module.
•
To establish an alarm Tag open the page "Create new tag..." via
Configuration
>
Tag setup
.
•
Enter here the following parameters:
Identification
Tag name
:
Alarm1
Page
:
Default
Tag description
: Comment
I/O server setup
Server name
: S73&400
Topic name
:
A
Address
:
DB1B13#3
Type
:
boolean
Alarm setup
Alarm enabled
: enable
option
Boolean alarm level
:
set to 1
•
Leave the other values on its default setting, enable the option "Then
edit notification" and click at [Add/Update only].
The dialog window "Alarm notification ..." is opened
•
Enter the following parameters:
SMS upon
:
enable the option ALM
SMS designation
:
here type in the telephone number with the
following structure: number,gsm,0
Enter each without spaces and always add to
telephone number ",gsm,0".
SMS subject
:
please type in the following text:
"Alarm 1: Error message - please confirm with
A1"
•
Click at [Update].
Acknowledge
alarm via SMS
Establishing an
alarm Tag