Manual VIPA TM-E
Chapter 3
Deployment TM-E
HB39E - TME - RE_900-1E660 - Rev. 09/11
3-37
To access the TM-E module via PPP connection the server for incoming
PPP connections is to be configured.
•
Here open the Web page of the TM-E module.
•
Navigate to the "Communication" page via
Configuration
>
System
setup
. Open the page "Incoming" in the navigation tree
Network
Connection
>
Modem
.
•
Activate the option "Server enabled".
•
Here enter the following parameters:
- "TM-E PPP server IP address": 202.0.0.240
- "PPP client IP address": 202.0.0.1
•
Accept the remaining default settings and click at [Update].
Configure your PC modem so that it may establish a connection to the TM-
E module. Here establish a DFÜ connection. More about this may be found
in the manual of your PC operating system.
Here please regard that User name and Password are identical to the
access data in you TM-E module.
The default access parameters are:
User name:
adm
Password: adm
Call your TM-E module via the PC modem.
Open as soon as the TM-E module reacts a DOS command window and
send a ping to the IP address 202.0.0.240. You should now get a
response. Else check your settings.
Configuration
Test the telephone
connection