IM 353-1DP00 - DP-V0 slave - Project engineering
For project engineering a DP master engineering tool can be used like the
Siemens SIMATIC manager. Here you assign the according Profibus DP
slave modules to the DP master.
A direct assignment takes place via the Profibus address that you set at
the DP slave address selector.
By installing the GSD file VIPA056B.gsd the IM 353-1DP00 is listed at the
hardware catalog as "VIPA_DP300V". After the installation of the GSD-file,
you'll find this at:
Profibus DP
> Additional Field devices> I/O > VIPA_System_300V
VIPA supplies a data medium with every Profibus module. This medium
contains among others all the GSD files of the VIPA Profibus modules.
Please install the file VIPA056B.gsd at your configuration tool. Details on
the installation of a GSD file are available from the manual supplied with
your configuration tool.
•
Mount your Profibus system.
•
Start your project engineering tool with a new project.
•
Configure a master system and create a new Profibus subnet.
•
For the project engineering of the IM 353-1DP00 take the
"VIPA_DP300V" from the hardware catalog and drag it to the DP master
subnet.
•
Enter a Profibus address between 1 and 99 into the properties of the DP
slave and set the same address at the address lever.
•
Parameterize the DP slave (see parameters).
•
Transfer your project to the PLC.
Diagnostic interrupt
The Profibus slave has as parameter the value "Diagnostic interrupt" that
you may activate via "YES" res. deactivate via "NO".
In delivery state, the diagnostic interrupt is activated. This causes the CPU
to branch into the OB 82 in case of an error. Here you may react to the
error and evaluate the diagnostic by using the SFC 13. Structure and
evaluation of the diagnostic of the IM 353-1DP00 is described at the
following pages.
Note
Every change in the arrangement of the modules must be followed by a
re-calculation of the bus parameters!