Chapter 4 CANopen
Manual VIPA System 300V
4-36
HB130E - IM - Rev. 08/26
Index
Sub-
index
Name
Type
Attr. Map. Default value
Meaning
0x1409 0
Number
of
Elements
Unsigned8 ro
N
0x02
Communication parameter for
the first receive PDOs, sub-
index 0: number of following
parameters
1
COB-ID
Unsigned32 rw
N
0xC00007C0
+ NODE_ID
COB-ID RxPD10
2
transm. type Unsigned8
rw
N
0xFF
Transmission type of the PDO
Index
Sub-
index
Name
Type
Attr. Map. Default value Meaning
0x1600 0
Number
of
Elements
Unsigned8
rw
N
0x01
Mapping parameter of the first
receive PDO; sub-index 0:
number of mapped objects
1
1st
mapped
object
Unsigned32 rw
N
0x62000108
(2 byte index,
1 byte sub-index,
1 byte bit-width)
2
2nd
mapped
object
Unsigned32 rw
N
0x62000208
(2 byte index,
1 byte sub-index,
1 byte bit-width)
...
...
...
...
...
...
...
8
8th mapped Unsigned32 rw
N
0x62000808
(2 byte index,
1 byte sub-index,
1 byte bit-width)
The first receive PDO (RxPDO1) is per default for the digital outputs.
Depending on the number of the inserted outputs, the needed length of the
PDO is calculated and mapped into the according objects.
For the digital outputs are organized in bytes, the length of the PDO can be
directly seen in sub-index 0.
If the mapping is changed, the entry in sub-index 0 has to be adjusted
accordingly.
Communication
parameter RxPDO10
Mapping
parameter
RxPDO1