Manual VIPA System 200V 

Chapter 2   Assembly and installation guidelines 

HB97E - PS-CM - Rev. 06/29 

 

2-7 

The following sequence shows the steps required for the removal of 
modules in a side view. 

 

• 

The enclosure of the module has a spring-loaded clip at the bottom by 
which the module can be removed from the rail.  

• 

Insert a screwdriver into the slot as shown. 

 

 

 

 

 

 

• 

The clip is unlocked by pressing the screwdriver in an upward direction. 

 

 

 

 

 

 

• 

Withdraw the module with a slight rotation to the top. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Attention!

 

Power must be turned off before modules are 
installed or removed! 

Please remember that the backplane bus is 
interrupted at the point where the module was 
removed! 

 

 

Removal 
procedure 

 

➡➡

 

 

Содержание System 200V CM

Страница 1: ...Manual VIPA System 200V PS CM Order No VIPA HB97E_PS CM Rev 06 29...

Страница 2: ...Lerrzeichen...

Страница 3: ...manual were verified with respect to the hard and software However we assume no responsibility for any discrepancies or errors The information in this manual is verified on a regular basis and any re...

Страница 4: ...ains general information about the System 200V i e dimensions installation and operating conditions Chapter 2 Assembly and installation guidelines This chapter provides all the information required fo...

Страница 5: ...on guidelines 2 1 Overview 2 2 Assembly 2 5 Wiring 2 8 Assembly dimensions 2 10 Installation guidelines 2 12 Chapter 3 Power supplies PS 3 1 Safety precautions 3 2 System overview 3 3 PS 207 2 Power s...

Страница 6: ...Contents Manual VIPA System 200V ii HB97E PS CM Rev 06 29...

Страница 7: ...ing guides are available in the manual an overall table of contents at the beginning of the manual an overview of the topics for every chapter an index at the end of the manual The manual is available...

Страница 8: ...zone The manual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using or commissioning t...

Страница 9: ...a summary The chapter also contains the general specifications of the System 200V i e dimensions installation and environmental conditions Below follows a description of Introduction of the System 20...

Страница 10: ...le to become inoperable or unusable Modules that have been damaged by electrostatic discharges may fail after a temperature change mechanical shock or changes in the electrical load Only the consequen...

Страница 11: ...s are installed directly on a 35mm DIN rail Bus connectors inserted into the DIN rail provide the interconnecting bus The following figure illustrates the capabilities of the System 200V System 200V d...

Страница 12: ...up to 4 rows In combination with a Profibus DP master and slave the PLC CPUs or the PC CPU form the basis for a Profibus DP network in accordance with DIN 19245 3 The DP network can be configured with...

Страница 13: ...1 2 3 4 5 6 7 8 9 I0 DI 8xDC24V SM 221 0 1 2 3 4 5 6 7 VIPA 221 1BF00 X 2 3 4 1 2 3 4 5 6 7 8 9 I0 DI 8xDC24V SM 221 0 1 2 3 4 5 6 7 VIPA 221 1BF00 X 2 3 4 1 2 3 4 5 6 7 8 9 I0 DI 8xDC24V SM 221 0 1 2...

Страница 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E PS CM Rev 06 29...

Страница 15: ...semble and wire a controller consisting of Systems 200V components Below follows a description of a general summary of the components steps required for the assembly and for wiring EMC guidelines for...

Страница 16: ...les You may use the following standard 35mm profile rail to mount the System 200V modules 35 mm 27 mm 15 mm 1 5 mm 35 mm 27 mm 7 5 mm 1 mm System 200V modules communicate via a backplane bus connector...

Страница 17: ...6 7 VIPA 221 1BF00 X 2 3 4 1 2 3 4 5 6 7 8 9 I0 DI 8xDC24V SM 221 0 1 2 3 4 5 6 7 VIPA 221 1BF00 X 2 3 4 1 2 3 4 5 6 7 8 9 I0 DI 8xDC24V SM 221 0 1 2 3 4 5 6 7 VIPA 221 1BF00 X 2 3 4 1 2 3 4 5 6 7 8 9...

Страница 18: ...3 4 1 2 3 4 5 6 7 8 9 I0 DI 8xDC24V SM 221 0 1 2 3 4 5 6 7 VIPA 221 1BF00 X 2 3 4 1 2 3 4 5 6 7 8 9 I0 DI 8xDC24V SM 221 0 1 2 3 4 5 6 7 VIPA 221 1BF00 X 2 3 4 1 2 3 4 5 6 7 8 9 I0 DI 8xDC24V SM 221...

Страница 19: ...module PC CPU and bus coupler 1 2 4 3 Modules are to install adjacent to each other Gaps are not permitted between the modules since this would interrupt the backplane bus A module is only installed p...

Страница 20: ...uter left location with the installation of your header module like CPU PC or bus coupler and install the peripheral modules to the right of this 1 2 4 3 Insert the module that you are installing into...

Страница 21: ...ded clip at the bottom by which the module can be removed from the rail Insert a screwdriver into the slot as shown The clip is unlocked by pressing the screwdriver in an upward direction Withdraw the...

Страница 22: ...signaling and power cables In contrast to screw terminal connections spring clip wiring is vibration proof The assignment of the terminals is contained in the description of the respective modules You...

Страница 23: ...ection shows the wiring procedure from above Insert a screwdriver at an angel into the square opening as shown Press and hold the screwdriver in the opposite direction to open the contact spring Inser...

Страница 24: ...re follow all the important dimensions of the System 200V 1tier width HxWxD in mm 76 x 25 4 x 74 2tier width HxWxD in mm 76 x 50 8 x 74 80 mm 60 mm 74 mm 88 mm ca 110 mm 84 mm 85 mm 76 62 mm 76 mm 2 7...

Страница 25: ...and installation guidelines HB97E PS CM Rev 06 29 2 11 84 46 mm 88 mm 4 66 mm 27 mm 8 cm 76 mm 24 mm 11 mm 85 mm 89 mm 89 mm 27 mm 8 cm 76 mm 12 cm 125 mm 91 mm 65 mm 24 mm 5 mm 11 mm 85 mm Function...

Страница 26: ...e causing illegal interference to the environment All System 200V components were developed for applications in harsh industrial environments and they comply with EMC requirements to a large degree In...

Страница 27: ...ta lines must be screened Analog lines must be screened Where low amplitude signals are transferred it may be advisable to connect the screen on one side of the cable only Attach the screening of cabl...

Страница 28: ...where it is not possible to install equipotential bonding conductors analog signals in the mV or A range are transferred foil type shields static shields are used Always use metallic or metallized co...

Страница 29: ...lies Below follows a description of the Power supply 2A Power supply 2A with terminal module Installation and wiring Technical data Topic Page Chapter 3 Power supplies PS 3 1 Safety precautions 3 2 Sy...

Страница 30: ...before commencing installation or maintenance work i e before you start to work on a power supply or the supply cable the main supply line must be disconnected disconnect plugs on permanent installati...

Страница 31: ...can use it as a separate external power supply The following power supplies are currently available PS 207 2 X 2 3 4 VIPA 207 1BA00 L N P E 100 240V AC 550 230mA 50 60Hz OH OL OK X1 1 2 3 4 OUT DC 24V...

Страница 32: ...0 60Hz OH OL OK X1 1 2 3 4 OUT DC 24V 2A 4A peak G DC 24V DC 24V The front of the power supply carries 3 LEDs for troubleshooting purposes The following table lists the significance and the respective...

Страница 33: ...ainst short circuits and have an output voltage of DC 24V with a total current of 2A max 24V 100 240V AC DC Danger You need to disconnect the power supply from the main power source before commencing...

Страница 34: ...3 4 1 2 3 4 DC 24V DC 24V X1 X4 X3 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 X3 1 2 3 4 5 6 7 8 9 10 11 X4 The front of the power supply carries 3 LEDs for troub...

Страница 35: ...short circuits protec ted and have an output voltage of DC 24V with a total current of max 2A 24V 100 240V AC DC Danger You need to disconnect the power supply from the main power source before comme...

Страница 36: ...main power source before commencing installation or maintenance work i e before you start to work on a power supply or the supply cable the main supply line must be disconnected disconnect plugs on pe...

Страница 37: ...on to open the spring contact Insert the stripped end of the interconnecting wire into the round hole You may use wires of a diameter of 0 08mm2 to 2 5mm2 When you remove the screwdriver the inserted...

Страница 38: ...48W 4A peak Efficiency typ 90 at Irated Power dissipation 5W at nominal load No load power 1 5W Status indicators LED via LEDs located on the front Operating conditions Operating temperature 0 C 55 C...

Страница 39: ...5W at the nominal load No load power 1 5W Status indicators LED via LEDs located on the front Operating conditions Operating temperature 0 C 55 C linear derating from 40 C to 55 C with 1 2W C Storage...

Страница 40: ...Chapter 3 Power supplies PS Manual VIPA System 200V 3 12 HB97E PS CM Rev 06 29...

Страница 41: ...st Ethernet mini switch This module completes the System 200V network technology The chapter concludes with the terminal modules These modules provide connection facilities for signaling cables as wel...

Страница 42: ...external power supply DC 5 24V CM 201 VIPA 201 1AA00 X 2 3 4 X2 X1 CM 201 VIPA 201 1AA40 X 2 3 4 X2 X1 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6 X3 X4 Type Order number Description CM 201 VIPA 201...

Страница 43: ...EDs on the front side 4 ports for 10 res 100MBit s plug and play through Auto MDI MDIX crossover for 100BASE TX and 10BASE T Auto Negotiation and Speed Auto Sensing for every port automatic switch bet...

Страница 44: ...nnecting an external power supply there is a connection jack available from VIPA under the order number VIPA 970 0CM00 Attention The power supply has to take place either internal via backplane bus or...

Страница 45: ...aximum terminal current 10A Construction Description Schematic diagram CM 201 VIPA 201 1AA00 X 2 3 4 X2 X1 1 2 3 1 Label 2 1st terminal strip 3 2nd terminal strip 1 2 3 4 5 6 7 8 9 10 11 X1 1 2 3 4 5...

Страница 46: ...current 10A Construction Description Schematic diagram 1 2 4 CM 201 VIPA 201 1AA40 X 2 3 4 X2 X1 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6 X3 X4 3 5 1 Label 2 1 st terminal strip 3 2nd terminal stri...

Страница 47: ...01 4 5 CM 240 4 3 PS 207 2 3 4 PS 207 2CM 3 6 System 200V Assembly 2 1 2 5 dimensions 2 10 Basics 1 1 Bus connector 2 2 Centralized system 1 4 Components 1 4 Decentralized system 1 4 Disturbances 2 12...

Страница 48: ...Index Manual VIPA System 200V A 2 HB97E PS CM Rev 06 29 M Stich...

Отзывы: