![VIPA System 200V CM Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/vipa/system-200v-cm/system-200v-cm_manual_1029240019.webp)
Manual VIPA System 200V
Chapter 2 Assembly and installation guidelines
HB97E - PS-CM - Rev. 06/29
2-5
Assembly
Please follow these rules during the assembly!
•
Turn off the power supply before you insert or remove any modules!
•
Make sure that a clearance of at least 60mm exists above and 80mm
below the middle of the bus rail.
80 m
m
60 m
m
•
Every row must be completed from left to right and it has to start with a
header module (PC, CPU, and bus coupler).
1
2
4
3
•
Modules are to install adjacent to each other. Gaps are not permitted
between the modules since this would interrupt the backplane bus.
•
A module is only installed properly and connected electrically when it
has clicked into place with an audible click.
•
Plug-in locations after the last module may remain unoccupied.
Note!
A maximum of 32 modules can be connected at the back plane bus. Take
attention that here the maximum
sum current
of
3.5A
is not exceeded.
[1] Header
module,
like PC, CPU, bus
coupler, if double
width
[2] Header
module
(single width)
[3] Peripheral
module
[4] Guide
rails
Содержание System 200V CM
Страница 1: ...Manual VIPA System 200V PS CM Order No VIPA HB97E_PS CM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 200V ii HB97E PS CM Rev 06 29...
Страница 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E PS CM Rev 06 29...
Страница 40: ...Chapter 3 Power supplies PS Manual VIPA System 200V 3 12 HB97E PS CM Rev 06 29...
Страница 48: ...Index Manual VIPA System 200V A 2 HB97E PS CM Rev 06 29 M Stich...