-13-
condensate
c. Drain restricted
c. Clean the drip tray and drain line
15. Condensate
inside ducts
a. Drain line restricted
b. Continually running not
stopping
c. Too cold supply air
a. Check for drain
b. raise
temperature
setting
or
increase defrost
c. Increase
air
flow
or
raise
temperature setting
16. Condensate
outside ducts
a. Duct not insulated
b. High humidity
c. Too cold supply air
a. Check for insulation
b. Use dehumidifier
c. Increase
air
flow
or
raise
temperature setting
17. Circuit tripping
a. Incorrect fuse or breaker
b. Incorrect wirings
c. Failed components
a. Check for proper fuse or breaker
b. Check for wirings and connections
c. Call service
18. Noisy
operation
a. Mounting area not firm
b. Loose parts
c. Compressor overloaded due
to improper condenser cooling
d. Defective components
a. Add support to improve installation
b. Check fan blades, bearings, washers,
tubing contact and loose screws.
c. Check for water flow
d. Call service for checking internal
loose, inadequate lubrication and
incorrect wirings
Содержание WM-2500SSRWC
Страница 17: ... 16 Fig 4 WM 25 65SFCR Evaporator Unit ...
Страница 27: ... 26 Fig 15 WM 6500SSRWC Electrical Wiring Diagram ...