B.  PS2 Dual Control 

 

 

 

Fig. 13 Adjustable Pressure Control 

 

III. 

Low ambient condition kit (if applicable)

 

 

A. 

The crankcase heater

 

 
The  crankcase  heater is installed at the bottom of the  compressor and shall be 
turned on all the time.  The heater is self-regulated. 
 
B. 

The condenser fan control

 

 

The  condenser  fan  control  is  installed  at  the  high  side.  It  closes  on  rise  of 
pressure. It is necessary to adjust the setting in the field to avoid fan short cycle. 
 
Head pressure setting: Cut in=170 psig; Cut out=110 psig; Differential=60 psig; 
 

 

 

Fig. 14 Condenser Fan Cycle Control 

 

Содержание WINE-MATE WM-12000SSD

Страница 1: ...D WM 6500SSD LA WM 8500SSD WM 8500SSD LA WM 12000SSD WM 12000SSD LA w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th he es se e i in ns st tr ru uc ct ti io on ns...

Страница 2: ...1 Important Safety Information...

Страница 3: ...2 Table of Contents Cellar Construction Guide 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 27 Warranty 30...

Страница 4: ...temperature surrounding the cellar shall not exceed the temperature of the cellar by more than 25 F No cellar walls shall receive direct sun or strong wind Lighting shall be of low wattage with a tim...

Страница 5: ...storage of wine like that in natural caves SSD evaporator units can be installed on the ceiling in the center of a wine cellar The evaporator units provide two way air supply for better operation SSD...

Страница 6: ...temperatures or lower insulations will cause reducing capacity and the cellar temperature may not be maintained at 55 F The specifications are listed as follows Model No Capacity Btu h Airflow CFM Ma...

Страница 7: ...ock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys pr...

Страница 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Страница 9: ...e regulation differential 4 AC anti short cycle delay min 10 hidden Con compress on with probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display...

Страница 10: ...ative humidity Use a separate hygrometer to monitor the humidity 10 How to set alarm call 1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the se...

Страница 11: ...ng Clean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Remo...

Страница 12: ...oling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost and turns off at 55 F of air temperature The average air temperature is 57 F and then...

Страница 13: ...rt capacitor overload protector compressor c Call service 9 Compressor running but condenser fan not running a Fan blade stuck b Incorrect or loose wirings c Failed motors d Fan cycle control a Check...

Страница 14: ...cessive condensate b High humidity causing excessive condensate c Drain restricted a Check for any air leak b Use drain line c Clean the drip tray and drain line 17 Condensate inside ducts a Drain lin...

Страница 15: ...Installation of the system must be done in accordance with all state and local building and electrical codes The condensing unit and evaporator unit are connected by a liquid line and an insulated suc...

Страница 16: ...WM 45SFCD 23 x 17 1 2 x 10 1 2 WM 450SCUR 18 x 14 x 12 115V 60HZ 1A 115V 60HZ 6A 20A 25 60 WM 4500SSD LA WM 45SFCD 23 x 17 1 2 x 10 1 2 WM 450SCUR LA 18 x 14 x 12 115V 60HZ 1A 115V 60HZ 7A 20A 25 60...

Страница 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 25 45SFCD Evaporator Unit...

Страница 18: ...17 Fig 5 WM 65 120SFCD Evaporator Unit Fig 6 WM 250 450SCUR Condensing Unit...

Страница 19: ...llar but the air probe must be located inside 2 The air probe shall be located in the wine cellar 5 ft above the floor or the air return area but it shall not be located in the air supply area or othe...

Страница 20: ...ll be below 50 F 1 Place the condensing units WM 250 1203SCUR in a properly ventilated location Otherwise heat exhausted by the condensing unit will build up and the cooling system will not operate pr...

Страница 21: ...ft long use both inverted U trap and suction accumulator to prevent liquid from flooding back to the compressor 3 If the condensing unit is located below the evaporator unit use inverted U trap to pr...

Страница 22: ...ings to charge refrigerant properly If the unit is equipped with a low ambient condition kit and installed in the summer add 15 more refrigerant If the low ambient condition kit is used turn off the c...

Страница 23: ...cking pressure control settings I The encapsulated pressure control if applicable Suction pressure setting fixed Cut in 32 psig Cut out 10 psig Fig 12 Fixed Pressure Control II The adjustable pressure...

Страница 24: ...e compressor and shall be turned on all the time The heater is self regulated B The condenser fan control The condenser fan control is installed at the high side It closes on rise of pressure It is ne...

Страница 25: ...k the subcooling first to see if the refrigerant charge is sufficient If the charge is not sufficient add more refrigerant Liquid must always be charged into the hide side when the compressor runs If...

Страница 26: ...al head pressure High superheat and normal to high subcooling 12 Low suction pressure and normal head pressure High superheat and normal subcooling 13 Low suction pressure and high head pressure High...

Страница 27: ...d components 4 Low pressure switch shutting down the system 5 high pressure switch shutting down the system 1 Check for proper voltage 2 Check all wirings and connections 3 Check start relay start cap...

Страница 28: ...he field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condens...

Страница 29: ...28 Fig 17 WM 2500 4500SSD LA Electrical Wiring Diagram Fig 18 WM 6500 12000SSD Electrical Wiring Diagram...

Страница 30: ...29 Fig 19 WM 6500 12000SSD LA Electrical Wiring Diagram...

Страница 31: ...ties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products...

Страница 32: ...USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED...

Отзывы: