- 19 -
1) Place the condensing units WM-250~1203SCUR in a properly ventilated
location. Otherwise, heat exhausted by the condensing unit will build up and
the cooling system will not operate properly.
2) Condensing unit shall be elevated to avoid possible flooding and shaded from
direct sun. It shall not be exposed to temperatures higher than 110 °F or
lower than 50 °F.
3) Leave minimum 5 ft clearance for the air exhaust side and leave minimum 1
foot clearance for the air intake side.
5. Refrigeration Piping and Leak Testing
NOTE
The line connector sizes of liquid filter and indicator, the valve
connector sizes of condensing unit or the line connector sizes of
evaporator unit may not be the same as the listed refrigeration line
sizes.
If the condensing unit is installed above the evaporator unit, use
the suction line one size smaller.
Expansion and solenoid valves have been installed on the liquid
line in the evaporator unit.
The line sizes and refrigerant charges are listed as follows.
Model No.
Equivalent
Line Set
Liquid
Line
Suction
Line
Drain Line
Recommended
Initial Charge
WM-2500SSA
WM-2500SSA-LA
<= 75 FT
1/4” OD
3/8” OD
7/8” MPT
R134a / 19 OZ
WM-4500SSA
WM-4500SSA-LA
<= 75 FT
1/4” OD
1/2” OD
7/8” MPT
R134a / 26 OZ
WM-6500SSA
WM-6500SSA-LA
<= 75 FT
1/4” OD
1/2” OD
7/8” MPT
R134a / 32 OZ
WM-8500SSA
WM-8500SSA-LA
<= 75 FT
3/8” OD
5/8” OD
7/8” MPT
R134a / 40 OZ
WM-12000SSA
WM-12000SSA-LA
<= 75 FT
3/8” OD
7/8” OD
7/8” MPT
R134a / 56 OZ
1) The piping starts from
à
condensing unit’s receiver discharge valve
à
liquid
filter
à
liquid indicator
à
liquid line
à
to evaporator unit’s liquid line
connection (assembled with solenoid valve and expansion valve)
à
suction
line connection
à
insulated suction line
à
to condensing unit’s suction valve.
2) If the line set exceeds 75 ft long, use both inverted U trap and suction
accumulator to prevent liquid from flooding back to the compressor.
3) If the condensing unit is located below the evaporator unit, use inverted U
trap to prevent liquid from flooding back to the compressor. If the elevation
difference is more than 10 ft, use both inverted U trap and suction
accumulator.
4) If the condensing unit is located more than 10 ft above the evaporator unit,
use U trap to aid oil returning to the compressor.
Содержание WINE-MATE WM-12000SSA
Страница 2: ...1 Important Safety Information...
Страница 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 25 120SFCA Evaporator Unit...
Страница 18: ...17 Fig 5 WM 250 450SCUR Condensing Unit Fig 6 WM 650 1203SCUR Condensing Unit...
Страница 28: ...27 Fig 17 WM 2500 4500SSA LA Electrical Wiring Diagram Fig 18 WM 6500 12000SSA Electrical Wiring Diagram...
Страница 29: ...28 Fig 19 WM 6500 12000SSA LA Electrical Wiring Diagram...