- 9 -
1. Condensing Unit
•
Place the condensing units WM150~650SCU in a
properly ventilated location. If it is not, heat
exhausted by the condensing unit will build up and
the cooling system will not operate properly.
•
Condensing unit shall be elevated to avoid possible flooding and shaded
from direct sun. It shall not be exposed to temperatures higher than 110
°
F or lower than 50
°
F (optional low ambient kit available).
•
Leave minimum 5 ft clearance for the exhaust side and leave minimum 1
foot clearance for the fresh air intake side.
CAUTION:
IF THE CONDENSING UNIT IS EQUIPPED WITH A LOW AMBIENT
CONDITION KIT, DO NOT TURN ON THE COMPRESSOR UNTIL THE
CONDENSING UNIT HAS BEEN POWERD FOR 24 HOURS.
2. Discharge/Suction Valve Operation (Condensing unit)
Back Position
: Normal operation, process and manometer port closed
Front Position
: Liquid/suction line connection closed
Middle Position
: All ports open for evacuation, charge and manometer reading
BACK POSITION FRONT POSITION MIDDLE POSITION
Fig. 8 ROTALOCK Valve Operation
BACK POSITION FRONT POSITION MIDDLE POSITION
Fig. 9 Base Valve Operation