ALARM SIGNALS
Code Description
Alarm Recovery
Probe alarms (P1) start a few seconds after the fault occurs in the related
probe; they automatically stop a few seconds after the probe restarts normal
operation. Check connections before replacing the probe. Temperature alarms
(“HA” and “LA”) automatically stop as soon as the temperature returns to a
normal value. “CA” Alarm (with i1F=PAL) recovers only by switching off and on
the instrument.
Temperature Set-Point
How to see the set-point
1.
Push and immediately release the SET key: the display will show the
Set-point value.
2.
Push and immediately release the SET key or wait for 5 seconds to
display the probe value again.
How to change the set-point
1.
Push the SET key for more than 3 seconds to change the Set point value;
2.
The value of the set point will be displayed and the “°C” or “°F” LED
starts blinking.
3.
To change the Set value, push
or
arrow keys within 10 seconds.
4.
To memorize the new set point value, push the SET key again or wait 10
seconds.
Manual Defrost
Push the DEF key for more than 2 seconds and a manual defrost will start.