background image

too far into the drier and contacting the screen. To facilitate the installation, place a slight bend in 
the capillary tube about 3/4inch from the end and insert into the drier. Remove the process tube 
adapter from the condenser outlet and prepare the tube for connection to the drier inlet. The drier 
inlet joint will be the only copper-to-steel connection which will require the silver solder and flux. 
To help prevent flux from entering the system, first insert the line from the condenser into the 
drier inlet, then apply the flux. Braze both the inlet and the outlet joints of the re-placement drier. 
 

3. Isolate and flush the remainder of the system 

Score and break the suction line close enough to the old compressor to be able to reconnect it to 
the replacement compressor later. Attach a process tube adapter to the evaporator side of the 
suction line. Connect the hand valve and hose from the recovery equipment to this adapter.    Be 
certain that the pressure in the charging cylinder is about 30 p.s.i.g. above ambient temperature.   
Start the recovery unit and open the hand valve to the suction line. Release four (4) ounces of 
R134a from the charging cylinder into the system. It will take about 15 minutes for the refrigerant 
to pass through the condenser, hot pipe, filter drier, capillary tube, evaporator, suction line and 
into the recovery system. This 15 minutes time can be utilized to remove the old compressor and 
prepare the new compressor by mounting into place and wiring electrically. Remember to leave 
the plugs in place until brazing. 
 

4. Complete compressor replacement 

Close valves to the recovery system. Re-move process tube adapters from both the suction and 
discharge lines. During final flush, remove old compressor, and install replacement compressor 
leave plugs in place until brazing. Connect and braze suction and discharge lines to the 
replacement compressor. You are now ready to add the temporary piercing valve to the drier 
process line and proceed with the sweep and final charging of the system. 
 

CAUTION:

 In order to prevent sealed contamination, the time of atmospheric exposure must be 

limited to 15 minutes. Do not pull the plugs from the new compressor until you are ready to make 
the connections.   
 

5. Sweep and Final Charge 

The sweep charge is a method of purging the sealed system of moisture, air and potential 
contaminants. Also during this procedure, the system may be checked for leaks before the final 
charge. If this procedure is followed as outlined, it will allow for the capture of 90-95 percent of 
the available refrigerant, thereby ensuring that the system will operate as designed. The sweep 
procedure for R134a refrigerant systems is made after the system has been repaired and/or 
flushed. Three (3) ounces of refrigerant R134a is added to the system, circulated by the 
compressor for 5 minutes and recovered. Since a new filter drier has already been installed, a 
high side process tube is available. Install a temporary access valve to this process tube close 
enough to the end of the tube so that the tube can be pinched closed behind the valve and the 
opening sealed shut after the valve is removed. Remember, no access valve is to be left on the 
sealed system. Connect a 1/4 inch flare tee to the access valve. Connect a quick coupler hand 
valve to each side of the tee. To one hand valve, connect the hose from the charging cylinder.   
To the other valve, connect the hose to the recovery system. The following steps take you 
through the sweep and final charge. 
 

Step 1.

    Set up of valves:    temporary access valve (C) piercing drier process tube, connected 

to flare tee, hand valve (A) to charging cylinder, hand valve (B) to recovery system. 

 

 

Step 2.

  With liquid refrigerant present to valve A, valve B closed and valve C open(C will 

Содержание VC100D

Страница 1: ...ING COOLING SYSTEM 4 ELECTRICAL AND CONTROL SYSTEM 5 COMPRESSOR ROOM VIEW AND PARTS LIST 6 HOW TO REVERSE THE DOOR SWING 7 HOW TO REPLACE THE MAIN PARTS 8 TROUBLESHOOTING 9 EXPLODED VIEW PARTS LIST Ca...

Страница 2: ...ycle to a specialized service center The gas inside the circuit may pollute the environment 11 When you discharge the refrigerant wear the protective safety glasses or goggle for eye safety 12 When yo...

Страница 3: ...System Air Forced Convection Type Compressor Model No VY35R00A B35C Type Hermetic Type LRA RLA 0 85 0 75 Overload Protector DRB21N61 A1 BR B 1 0 K 6 1 A 1 1 0 9 PTC Starter QP2 4R7 Q P 2 1 5 Oil Mine...

Страница 4: ...ermetic Type Hermetic Type LRA 12 5 8 1 12 5 8 1 RLA 0 80 0 55 0 80 0 55 Overload Protector 4TM232VH BYY B35 120 4TM232V HBYY B35 120 PTC Starter QP2 4 7 B 3 QP2 15 QP2 4 7 B 3 QP2 15 Oil ISO8 ISO1 0...

Страница 5: ...metic Type Hermetic Type LRA 12 5 8 1 12 5 8 1 RLA 0 80 0 55 0 80 0 55 Overload Protector 4TM232VH BYY B35 120 4TM232V HBYY B35 120 PTC Starter QP2 4 7 B 3 QP2 15 QP2 4 7 B 3 QP2 15 Oil ISO8 ISO1 0 17...

Страница 6: ...c Type Hermetic Type LRA 12 5 8 7 12 5 8 7 RLA 0 80 0 65 0 80 0 65 Overload Protector 4TM232VH BYY B40 120 B 4TM232V HBYY B40 120 B PTC Starter QP2 4 7 B 3 QP2 12 B QP2 4 7 B 3 QP2 12 B Oil ISO8 ISO1...

Страница 7: ...ype Hermetic Type LRA 12 5 8 7 12 5 8 7 RLA 0 80 0 65 0 80 0 65 Overload Protector 4TM232VH BYY B40 120 B 4TM232V HBYY B40 120 B PTC Starter QP2 4 7 B 3 QP2 12 B QP2 4 7 B 3 QP2 12 B Oil ISO8 ISO1 0 1...

Страница 8: ...pe Hermetic Type LRA 20 5 10 2 20 5 10 2 RLA 1 28 0 7 1 28 0 7 Overload Protector 4TM319LFB ZZ B60 120 B 4TM319LF BZZ B60 120 B PTC Starter QP2 4 7 B 3 QP2 12 B3 QP2 4 7 B 3 QP2 12 B3 Oil SH 5 WF7 A 1...

Страница 9: ...ermetic Type Hermetic Type LRA 20 5 10 2 20 5 10 2 RLA 1 28 0 7 1 28 0 7 Overload Protector 4TM319LFB ZZ B60 120 B 4TM319LF BZZ B60 120 B PTC Starter QP2 4 7 B 3 QP2 12 B3 QP2 4 7 B 3 QP2 12 B3 Oil SH...

Страница 10: ...rmetic Type LRA 20 5 10 2 20 5 10 2 RLA 1 28 0 7 1 28 0 7 Overload Protector 4TM319LFB ZZ B60 120 B 4TM319LF BZZ B60 120 B PTC Starter QP2 4 7 B 3 QP2 12 B3 QP2 4 7 B 3 QP2 12 B3 Oil SH 5 WF7 A 180ml...

Страница 11: ...etic Type Hermetic Type LRA 20 5 10 2 20 5 10 2 RLA 1 28 0 7 1 28 0 7 Overload Protector 4TM319LFB ZZ B60 120 B 4TM319LF BZZ B60 120 B PTC Starter QP2 4 7 B 3 QP2 12 B3 QP2 4 7 B 3 QP2 12 B3 Oil SH 5...

Страница 12: ...ling System Air Forced Convection Type Compressor Model No JK1111HY D53CY Type Hermetic Type LRA 12 5 8 1 RLA 0 80 0 55 Overload Protector 4TM232VH BYY B35 120 PTC Starter QP2 4 7 B 3 QP2 15 Oil ISO8...

Страница 13: ...1110Y JK1111HY JM1110Y Type Hermetic Type Hermetic Type LRA 12 5 8 7 12 5 8 7 RLA 0 80 0 65 0 80 0 65 Overload Protector 4TM232VH BYY B40 120 B 4TM232V HBYY B40 120 B PTC Starter QP2 4 7 B 3 QP2 12 B...

Страница 14: ...10Y JK1111HY JM1110Y Type Hermetic Type Hermetic Type LRA 12 5 8 7 12 5 8 7 RLA 0 80 0 65 0 80 0 65 Overload Protector 4TM232VH BYY B40 120 B 4TM232V HBYY B40 120 B PTC Starter QP2 4 7 B 3 QP2 12 B QP...

Страница 15: ...ooling System Air Forced Convection Type Compressor Model No JK1111HY JM1110Y Type Hermetic Type LRA 12 5 8 7 RLA 0 80 0 65 Overload Protector 4TM232VH BYY B40 120 B PTC Starter QP2 4 7 B 3 QP2 12 B O...

Страница 16: ...JM1080FY JM1080FY Type Hermetic Type Hermetic Type LRA 12 8 12 8 RLA 1 25 1 20 1 25 1 20 Overload Protector B86 120 B B86 120 B PTC Starter QP2 4 7 B QP2 4 7 B Oil ISO8 ISO10 175ml ISO8 ISO10 175ml C...

Страница 17: ...g System Air Forced Convection Type Compressor Model No NU1112FY Type Hermetic Type LRA 13 3 RLA 1 28 1 15 Overload Protector 5TM283PFBZZ PTC Starter QP2 4 7 B3 Oil ISO7 WF 7A 180ml Condenser Fan Moto...

Страница 18: ...s with Without Solenoid Valve 1 Compressor 2 Spiral Tube Not available for some models 3 Condenser Fan Not available for some models 4 Condenser 5 Hot Pipe 6 Process Tube 7 Filter Drier 8 Capillary 9...

Страница 19: ...h Solenoid Valve 1 Compressor 2 Spiral Tube 3 Condenser Fan 4 Condenser 5 Hot Pipe 6 Process Tube 7 Filter Drier 8 Solenoid Valve 9 Capillary 10 Evaporator Fan 11 Accumulator 12 Evaporator 13 Suction...

Страница 20: ...or into a liquid The hot pipe is the first part of the condenser routed around the cabinet to help prevent moisture formation The filter dryer is installed at the end of the condenser to capture moist...

Страница 21: ...dels the inlet side will connect to the discharge pipe of compressor and the outlet to filter dryer it is non replaceable Evaporator The evaporator is a fin tube type within the rear side of cabinet a...

Страница 22: ...ust be no smoking area No ignitable factors must be present Utilities Refrigerant cylinder MAX NET 300g Manometer Vacuum pump 600L min Piercing Clamp Quick coupler Hoses 5m 1EA 1m 3EA LOKRING Portable...

Страница 23: ...e vacuum pump simultaneously make sure the pump valve is closed Connect the charging hose that is connected to the refrigerant R600a cylinder to the Schrader valve installed on the service tube Then c...

Страница 24: ...of System Flush Procedure C Proceed with the following flush procedure D After flushing procedure is completed continue with the normal sweep and final charging procedure SYSTEM FLUSH PROCEDURE 1 Iso...

Страница 25: ...lugs in place until brazing Connect and braze suction and discharge lines to the replacement compressor You are now ready to add the temporary piercing valve to the drier process line and proceed with...

Страница 26: ...g the system If the system does not operate properly long run periods warmer than normal temperatures the trouble may be caused by one of the following conditions 1 Restricted Capillary Tube The openi...

Страница 27: ...floor A heat exchanger separation will also cause this symptom An undercharged system depending on the degree of undercharge will operate with temperatures above normal and the compressor run time wil...

Страница 28: ...Fahrenheit and Celsius degree will be ON In Eco Demo mode the compressor and all fan motors are OFF NOTE To perform the multi key function press and hold the first key then press the rest key the req...

Страница 29: ...ully active again 4 1 3 OTHER FUNCTIONS Temperature Memory Function In the event of a power interruption power surge breaker switch etc the unit can remember the previous temperature settings and when...

Страница 30: ...tor positioned in the bottom divider When the set temperature of the lower zone is lower than the storage temperature Fan F2C will operate When the set temperature of upper zone for dual zone or middl...

Страница 31: ...E Press and hold the LIGHT and UP the controls of upper zone for dual zone models the controls of lower zone for three zone models keys at the same time for 5 seconds with power ON the indicator light...

Страница 32: ...MP F1C RT1 RT2 TCJ POWER D XH DOOR SWITCH N A 4 2 3 For dual zone models without solenoid valve For control panel inside the cabinet BK BK TCJ D1 XH TCJ POWER D XH RED WH M RED WH M t BK BK BK RED t W...

Страница 33: ...OMPRESSOR YE GN OLP STARTER YE GN BL BN HEATER2 M M RED RED WH WH F2H F2C DOOR SWITCH N A Air Door M TCJ FM 4 2 4 For dual zone models with solenoid valve BK BK TCJ D0 XH TCJ POWER D XH RED WH M RED W...

Страница 34: ...K BL WH COMPRESSOR YE GN OLP STARTER YE GN BL BN HEATER2 t BK BK t WH WH t BL BL RT1 RT2 RT3 RED WH M RED WH M BK RED RED RED BK F0 LAMP F1C F3H F3C BK M RED WH M RED WH M RED WH F1H N A F2H F2C M M T...

Страница 35: ...4 3 2 Control PCB for Dual Zone Upper Control Unit of Three Zone...

Страница 36: ...4 3 3 Control PCB for Single Zone Lower Control Unit of Three Zone...

Страница 37: ...25 32 18 4 23 24 19 6 21 35 20 8 19 63 21 10 18 07 22 12 16 65 23 14 15 35 24 16 14 17 25 18 13 10 26 20 12 11 27 22 11 21 28 24 10 39 29 25 10 00 30 26 9 63 31 28 8 94 32 30 8 30 33 32 7 72 34 34 7 1...

Страница 38: ...l Box of Compressor 3 Process Pipe 4 Electrical Box Power PCB inside 5 Compressor 6 Suction Pipe 7 Discharge Pipe 8 Condenser Fan Motor Not available for some models 9 Drainage Hose 10 Outlet Tubing o...

Страница 39: ...ep is not needed 2 Remove the bottom hinge 5 by unscrewing the four lock screws 6 Be careful to hold the glass door firmly after removing the screws Fig 2 3 Gently pull down to remove the glass door f...

Страница 40: ...mbly on the left designated position and tighten it after the door is leveled 9 Transfer the handles plugs to the opposite positions and then reassembly the ventilation grilles if need 6 2 DESIGN 2 Fo...

Страница 41: ...fittings on the left hand side of cabinet Fig 4 5 Unscrew and transfer door supporter 10 to the opposite side At the same time remove the stopper pin 7 of bottom hinge to the opposite designated posi...

Страница 42: ...emoving the screws And then gently pull down to remove the upper glass door 15 from the top hinge and place it on a padded surface to avoid the risk of damage Then remove the right top hinge 10 Fig 5...

Страница 43: ...rt by unscrewing the screws 4 Carefully remove the control panel film 1 2 Unscrew the four bolts 2 that secure the top insert to the cabinet 3 Remove the top insert 6 4 Disconnect the cable from the c...

Страница 44: ...B 2 5 Dismantle the PCB supporter 3 from the PCB box 6 Then carefully remove the control PCB from the PCB supporter Now you can replace the control PCB c F 6 5 4 3 2 1 7 8 7 1C REPLACING THE CONTROL P...

Страница 45: ...fixing glue Sliding out and replace the control PCB 5 Remove the two screws 1 that secure the top plate 3 of middle divider to the upper air channel cover And then remove the top plate of middle parti...

Страница 46: ...rews 1 that secure the top plate 3 of middle divider to the upper air channel cover And then remove the top plate of middle divider 6 Disconnect the wires to fan motor F2C 9 7 Remove the four screws t...

Страница 47: ...the electrical box base 4 electrical box cover 7 and Power PCB 5 4 Disconnect the cables from the Power PCB and then you can replace the Power PCB 3 2 5 4 1 7 6 7 3a REPLACING THE POWER PCB FOR VC7S...

Страница 48: ...mly after removing the screws Pull down to remove the glass door and place it on a padded surface to prevent scratching it 2 3 1 4 5 2 Remove the two screws 3 that secure the ventilation grille to the...

Страница 49: ...ne IMPORTANT Pls insert the new LED light PCB with correct polarity 2 1 7 5A REPLACING THE LED LIGHT 1 Remove all shelves 2 Remove the screw 1 For the new design the step of removing the screw is not...

Страница 50: ...channel cover and then you can replace the evaporator fan motor 3 2 1 6 4 5 7 7 REPLACING THE PTC HEATER HEATER FAN MOTOR AND TEMPERATURE SENSOR IN THE LOWER ZONE FOR DUAL ZONE MODELS 1 Remove all sh...

Страница 51: ...8 and evaporator 9 and then you can replace them 6 Remove the fours screws 5 that secure the fan motor F1C 7 to the air channel cover and then you can replace the evaporator fan motor 1 2 3 4 7 9 8 5...

Страница 52: ...s to fix the evaporator assembly to the cabinet 8 Replace the evaporator assembly and install the new one to the cabinet 9 After replacing the evaporator assembly make sure to install back the four se...

Страница 53: ...clips previously removed 8 Connect the compressor leads 9 Solder a short piece of tubing to the process tube approximately 150mm 6 inches long Connect the refrigerant tubing to the compressor stubs 10...

Страница 54: ...ube from the old condenser 4 3 With assistance tilt the cabinet side and remove the screws 2 which secure the condenser to the cabinet bottom 4 Install the new replacement condenser to the cabinet by...

Страница 55: ...more than 1 16 1 5mm on the hinge side causing a poor seal elsewhere around the top The distance between the door and cabinet is greater at the top than at the bottom or vice versa 4 If one or more o...

Страница 56: ...re often than necessary Close door properly Check the door seal and clean or replace The light does not work Appliance is not connected to a power supply The circuit breaker tripped or a blown fuse Th...

Страница 57: ...The icon is lit up and flashing in the temperature display The display temperature is out of the range Only temperatures within the range 0 99 F 9 37 C the appliance can display will be shown If the t...

Страница 58: ...zone 1 Is the ambient temperature too high more than 35 C 2 Is he ventilation blocked 3 Is the evaporate fan motor in the upper zone failed 4 Is the condenser fan motor failed 5 Is the temperature se...

Страница 59: ...e condenser warms in proportion as the evaporator cools The process repeats again Moisture in the refrigerant causes the malfunction Replace the refrigerant 2 The condenser is cold The evaporator is n...

Страница 60: ...n PCB is normal No LED temperature display or indicator illuminated in the control panel Some LEDs do not light No response when touching the control marks For this kind of symptom double check to see...

Страница 61: ...wiring 2 To Check The Fan Motor in Middle Partition Disconnect the unit from the source Remove the top of middle partition Disconnect the fan motor lead connector from the cable Connect the motor to a...

Страница 62: ...nd set the temperature control to a cold setting If the compressor starts the overload is defective and must be replaced If the compressor fails to start check for a defective start relay or compresso...

Страница 63: ...the start mode The compressor could start but the overload protector will trip and eventually trip continuously 2 An Open Circuit Should under normal conditions allow the compressor to start Under a h...

Страница 64: ...l working components In spite of this technology your model may make sounds that are unfamiliar Normal operating sounds may be more noticeable because of the unit s environment Hard surfaces such as c...

Страница 65: ...freezing instead that the right lower zone of the model is not cooling pls check the solenoid valve as below Dismantle the POWER PCB box Connect the solenoid valve directly to the external power Conne...

Страница 66: ...ower PCB is failed Replace the Power PCB The Control PCB is failed Replace the Control PCB The connecting wire is failed such as the screw has made the wires short circuit Reroute a new wire 8 4 19 DS...

Страница 67: ...as it remains constant 8 5 3 What is the ideal humidity for wine Humidty between 60 70 is a superlative range in which to store wine High humidity levels keep moisture inside the bottle thus preventi...

Страница 68: ...er the other goes higher etc This is normal The temperature set for the LOWER ZONE must always be the same or higher than that in the UPPER ZONE So when the user is adjusting the set temperature for o...

Отзывы: