Three rocker push buttons, to complete with 1 or 2-module 
buttons - 3 modules.

Device to be used as three single buttons or one single and one double, depend-
ing on the button.

CHARACTERISTICS.

• Rated supply voltage: BUS 29 V
• Input: 16 mA
• Button: 1 double, 1 single or 3 single ones.
• Terminals: TP BUS
• Possible functions:
- ON/OFF switch
- dimmer control
- roller shutter control
- activation of 2 scenarios.
• 

Consist with:

- By-me flush and surface mounting control units, rel.2.0 and next
- By-me 2-module control units, rel. 2.0 and next

CONFIGURATION.

FOR THE OPERATIONS OF INSTALLATION AND CONFIGURATION, SEE THE 
By-me SYSTEM INSTRUCTIONS MANUAL ATTACHED TO THE CONTROL UNIT.

Configuration must be done with the device without the button to be able to 
press the central configuration button.
The device can be used as three single buttons or one double push-button and 
a single one.
• Functional blocks: 3, each functional block can belong to at most 4 groups.
• Selecting the functional block (configuration): during group creation, when the 

control unit requires pressing the device button:

- press the configuration button;
- if the device must be configured as three single push-buttons, within 3 s, press 

the right-hand button to select the right functional unit, the middle button to 
select the middle functional unit or the left-hand button to select the left func-
tional unit; the red LED illuminates.

   If none of the three buttons is pressed within approximately 3 s the red LED will 

light up; in this case the selected functional unit is the third one, the one related 
to the actuator. 

- if the device must be configured used as a double and a single push-button, 

proceed as follows:

• configure the left functional unit in the case in which you want a push-button 

with two modules on the left of the device (left middle button) and then 
configure the right functional unit (right button);

• configure the middle functional unit in the case in which you want a push-but-

ton with two modules on the right of the device (middle right button) 
and then configure the left functional unit (left button). 

- the red LED will come on and the control unit will configure the functional block; 

at the end of the operation the red LED will go out.

PARAMETERS.

• For each functional block it is possible to set the operating mode:
- ON/OFF button;
- dimmer control button;
- roller shutter control button;
- scenario control.
• Operation as a dimmer control button:
- pressing the key at the top for less than 0.5 s lights up the load with the dim-

ming at the saved point;

- pressing the key at the top for more than 0.5 s increases brightness until it is 

released;

- pressing the key at the bottom for more than 0.5 s decreases brightness until it 

is released;

- pressing the key at the bottom for less than 0.5 s switches off the load.
• Operation as a roller shutter control button:
- pressing the key at the top for more than 0.5 s opens the shutter completely; it 

stops when fully open or when briefly pressing the key (either at the top or bottom);

- pressing the key at the bottom for more than 0.5 s closes the shutter com-

pletely; it stops when fully closed or when briefly pressing the key (either at the 
top or bottom);

- use only roller shutters with a built-in limit switch.
• LED parameters:
- LED off;
- LED with normal operation (on if the associated actuator is ON);
- LED with reverse operation;
- LED always on for location in the dark;
- central LED with normal operation (Double button);
- central LED with reverse operation (Double button);
- central LED always on for location in the dark (Double button).

  If the functional block belongs to more than one group, the “LED with normal 

operation” and “LED with reverse operation” parameters are not available. In 
these cases the control is confirmed by a LED status change for 3 s.

  If a double key is used, it is necessary to set the central LED behaviour to make 

the status visible. In this case, configure the left button if the double button is 
on the left of the device or the middle button if the double button is on the right.

• Default parameters: the buttons are set as ON/OFF push-buttons (step step) and 

LED in normal operation. 

INSTALLATION RULES.

Installation should be carried out by qualified personnel in compliance with the 
current regulations regarding the installation of electrical equipment in the country 
where the products are installed.

CONFORMITY.

EMC directive
Standard EN 50428.

Caption:

A: Configuration button
B: LED
C: Terminals TP BUS 

B

A

FRONT AND BACK VIEW. 

 

C

WEEE - Information for users

If the crossed-out bin symbol appears on the equipment or packaging, this means the 
product must not be included with other general waste at the end of its working life. The 
user must take the worn product to a sorted waste center, or return it to the retailer when 
purchasing a new one. Products for disposal can be consigned free of charge (without 
any new purchase obligation) to retailers with a sales area of at least 400 m

2

, if they 

measure less than 25 cm. An efficient sorted waste collection for the environmentally 
friendly disposal of the used device, or its subsequent recycling, helps avoid the potential 
negative effects on the environment and people’s health, and encourages the re-use and/
or recycling of the construction materials.

Отзывы: