By-alarm

01710

By-alarm configurable 4-output expansion module with change-over 
relay 3 A 24 V.

TECHNICAL CHARACTERISTICS

• Power supply: 12 V ± 20%
• Absorption: 82 mA max
• Outputs: 4 with change-over relays, voltage-free, programmable in all the modes 

contemplated by the control panel.

• Connections: with 4 wires to one of the serial ports for connection to the RS485 bus
• Operating temperature: -10..+40 °C (indoor use)
• Dimensions: 76x62 mm
• Degree of safety: 2 (EN 50131-3)
• Ambient class: II (EN 50131-3)

INSTALLING THE EXPANSION MODULES

The module is connected to the control panel to one of the serial ports, following 
the instructions given in the control panel's installation manual and respecting the 
warnings.
• For installation, use halogen-free shielded cables suitable for installation with 

Category 1 power cables (U0 = 400 V) such as cable art. 01733 (2x0.50 
mm

2

+2x0.22 mm

2

). 

• For the power supply, use wires with a minimum cross-section of 0.50 mm

2

 observ-

ing the c and - polarity. 

• Connect the signal cables A and B using conductors with a minimum section equal 

to 0.22 mm

2

• The shielding must be connected to the negative on the control panel side and left 

free on the expansion module side. 

ADDRESSING THE EXPANSION MODULES

For them to be recognised by the control panel, the expansion modules need to be 
addressed by setting the DIP-switches on the printed circuit board; the settings that 
can be made are listed in the following table:

EXPANSION NO.

DIP-SWITCH NO.

1

2

3

4

5

6

EXPANSION 1

OFF

OFF

OFF

OFF

OFF

OFF

EXPANSION 2

ON

OFF

OFF

OFF

OFF

OFF

EXPANSION 3

OFF

ON

OFF

OFF

OFF

OFF

EXPANSION 4

ON

ON

OFF

OFF

OFF

OFF

EXPANSION 5

OFF

OFF

ON

OFF

OFF

OFF

EXPANSION 6

ON

OFF

ON

OFF

OFF

OFF

EXPANSION 7

OFF

ON

ON

OFF

OFF

OFF

EXPANSION 8

ON

ON

ON

OFF

OFF

OFF

EXPANSION 9

OFF

OFF

OFF

ON

OFF

OFF

EXPANSION 10

ON

OFF

OFF

ON

OFF

OFF

EXPANSION 11

OFF

ON

OFF

ON

OFF

OFF

EXPANSION 12

ON

ON

OFF

ON

OFF

OFF

EXPANSION 13

OFF

OFF

ON

ON

OFF

OFF

EXPANSION 14

ON

OFF

ON

ON

OFF

OFF

EXPANSION 15

OFF

ON

ON

ON

OFF

OFF

EXPANSION 16

ON

ON

ON

ON

OFF

OFF

Caution: The maximum number of expansion modules that can be installed 
depends on the type of control panel used.  
If the addressing made with the DIP-switches is changed with the module 
switched on, to make it operational you need to press the push-button PB1 or 
power cycle the device.

Amber LED  

The amber led on the expansion module lets you control functionality as follows:
• 

On steady

: module properly powered but no serial communication.

• 

Blinking at a frequency of 1 s

: module powered correctly and receiving serial com-

munications but these are sent with an incorrect address or no configuration of the 
device in the control panel.

• 

Blinking with one short pulse every second

: module powered properly and correct 

serial communication.

FEATURES OF THE MODULE 01710

The circuit with which the device is made has 4 single changeover relay outputs that 
can be programmed in all the modes contemplated by the control panel to which 
they are connected.
The push-buttons protecting against opening 

PB2

 and against removal 

PB3

 can be 

cut off by closing the relevant jumpers alongside the buttons. When commissioning 
the control panel, the tamper-proof cut-off jumpers must be removed to make the 
protections active so as not to invalidate the IMQ–security systems certification. 

Recessed connector

The module has a recessed connector; 

it must not be used under any circum-

stances as it is for internal testing; improper use may damage the circuit.

FRONT VIEW.

CONNECTIONS. 

CN5

20

D
E

A B

RS 485

SW 1

PB 1

1

ON

2

3

4

5

6

OFF

RELÈ 4

RELÈ 3

RELÈ 2

RELÈ 1

C

NC
NO

C

NC
NO

C

NC
NO

C

NC
NO

D
E

A B

RS 485

CN2

LED

a b

1

3

1

10

OFF

relè 1

relè 2

relè 3

relè 4

 

It is recommended to use the output RELAYS for signalling and not to 

control loads.

• For normal operation the jumper on CN2 must always be positioned 

between pins 1 and 2.  

01700-01700.120

01703-01703.120

01710

RS485 bus line

DIP-switch 
for setting
address

Reset button 

PB1

Connector 
not used

Anti-opening 
cut-off 

S2

Outputs

Jumper on CN2

Tear-proof 
cut-off 

S1