11
VIMAR group
ETS parameters and communication objects
COMMUNICA
TION OBJECTS
KNX weather station
Reference ETS parameters
Behaviour in the event of a power failure and when
power is restored.
Behaviour if there is no Bus voltage or auxiliary voltage:
The device transmits no data.
Behaviour if there is no Bus voltage or auxiliary voltage and
subsequent programming or restarting:
The device sends all the measured values, control outputs and
the status of the logic gates according to the behaviour set by
the parameters in the "General Settings". When powering up,
information will be sent with a settable delay.
General settings
General settings
ETS text
Available values
Comment
[
Default value
]
Send measured values
periodically all
5 s ... 2 h
[5 s]
Send control outputs peri-
odically all
5 s ... 2 h
[5 s]
Send logic outputs
periodically all
5 s ... 2 h
[5 s]
Logic input communication
objects
do not enable
enable
[do not enable]
Night control output com-
munication object
Do not send
Send with change
Send reversed with
change
Send with change and
cyclically
Send reversed with
change and cyclically
[Send with change]
Rain control output com-
munication object
Do not send
Send with change
Send reversed with
change
Send with change and
cyclically
Send reversed with
change and cyclically
[Send with change]
Control output transmission
delay after Power up and
programm.
5 s ... 2 h
When powering up
and after program-
ming, the weather
station waits for the
set time delay before
transmitting the
control outputs.
[10 s]
Maximum speed of the
telegram
1... 20 telegrams
per second
[5 telegrams per
second]