Vimar 01504.2 Скачать руководство пользователя страница 9

   9

ETS-Parameters line coupler

ETS-Text

Selection
[

Factory default]

Comment

Configuration

groups: filter, physical: block groups, physical: filter 
groups: route, physical: filter groups, physical: route 
configure

[groups, physical: filter]

Block

: no telegram is routed.

Filter

: only telegrams are routed which are entered in the filter table.

Route

: the telegrams are routed.

Configure: the following parameters can be set manually.

This parameter is to be set depending on the planed configuration.

Group telegrams

1. transmit all 

(not recommended)

2. block
3. filter

[filter]

1. All group telegrams are transmitted.
2. No group telegram is transmitted.
3. Only Group telegrams entered in the filter table are routed.
ETS3/4 produces the filter table automatically.

Main group
telegrams 14/15

1. transmit all
2. block
[

transmit all]

1. Group telegrams with the sub group 14 or 15 (e.g. 14/1) are routed.
2. Group telegrams with the sub group 14 or 15 (e.g. 14/1) are not routed.

Physical telegrams

1. transmit all 

(not recommended)

2. block
3. filter

[filter]

1. All Physical telegrams are transmitted.
2. No Physical telegram is transmitted.
3. Depending on the physical address only Physical telegrams are routed.

Physical:
Repetition when
errors on main line

1. no
2. normal
3. reduced

[normal]

If a transmission error (e.g. due to missing receiver) is found after sending a 
Physical telegram on the main line:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once

Group:
Repetition when
errors on main line

1. no
2. normal
3. reduced

[normal]

If a transmission error (e.g. due to missing receiver) is found after sending a 
Group telegram on the main line:
1. Physical telegrams are not repeated.
2. Physical telegrams are repeated up to three times.
3. Physical telegrams will be repeated only once.

Telegram
confirmations on line

1. if routed 
2. always

[if routed]

1.  Only telegrams which are to be routed are confirmed on the main line 

(ACK).

2. Each telegram on the main line is confirmed (ACK).

Send confirmation
on own telegrams

1. yes
2. no

[no]

1.  Every telegram on the main line is confirmed with its own ACK (from the 

Line coupler).

2. No confirmation with own ACK

 

See note below.

Fig. 7: Sub line configuration

Please note:

If the parameter “Send confirmation on own telegrams” is set to yes the line coupler will send an ACK systematically on any own routed telegram.

6.4 Sub line

Содержание 01504.2

Страница 1: ...Installer manual BUILDING AUTOMATION 01504 2 Line Field coupler KNX standard...

Страница 2: ...Contents...

Страница 3: ...ode 6 4 3 Function button 6 4 3 1 Manual function 6 4 3 2 Factory reset 6 5 Application description line coupler 7 6 ETS Parameters line coupler 7 6 1 Settings 7 6 2 General 8 6 3 Main line 8 6 4 Sub...

Страница 4: ...ally addressed telegrams in this document named Physical telegrams or according to the built in filter tables for group oriented communication Group telegrams Compared to other similar products the 01...

Страница 5: ...dress filtering status LED 7 Programming LED A Function button B Program button C KNX main line D KNX sub line 3 1 Installation example 01501 2 POWER SUPPLY UNIT L N AUX KNX 30V KNX 120 240V 50 60Hz 3...

Страница 6: ...e With the Programming button the device can be switched between Normal Mode and Program Mode To download the physical address to the device this function is essential After the download the 01504 2 a...

Страница 7: ...er that is set by ETS With the parameters Repetitions if errors this function can be adjusted separately for both con nected lines The default settings of these parameters should be retained 6 ETS Par...

Страница 8: ...f automatically Manual function disabled pass all telegrams pass physical telegrams pass group telegrams pass all telegrams Telegram routing configuration for the Manual Function Fig 5 General Fig 6 M...

Страница 9: ...3 Depending on the physical address only Physical telegrams are routed Physical Repetition when errors on main line 1 no 2 normal 3 reduced normal If a transmission error e g due to missing receiver i...

Страница 10: ...filter 1 All group telegrams are transmitted 2 No group telegram is transmitted 3 Only group telegrams entered in the filter table are routed ETS3 4 produces the filter table automatically Sub group t...

Страница 11: ...Line repeater has to be downloaded to the device Under the Information tab this configuration can be changed by the menu Change Application Program After changing the configuration the filter table e...

Страница 12: ...ams will be repeated only once Group Repetition when errors on main line 1 no 2 normal 3 reduced reduced If a transmission error e g due to missing receiver is found after sending a Group telegram on...

Страница 13: ...d up to three times 3 Physical telegrams will be repeated only once Group Repetition if errors on the sub line occur 1 no 2 normal 3 reduced reduced If a transmission error e g due to missing receiver...

Страница 14: ...Viale Vicenza 14 36063 Marostica VI Italy www vimar com 01504 2 EN 03 2102...

Отзывы: