Installer manual
BUILDING AUTOMATION
01504.2
Line/Field coupler KNX standard
Страница 1: ...Installer manual BUILDING AUTOMATION 01504 2 Line Field coupler KNX standard...
Страница 2: ...Contents...
Страница 3: ...ode 6 4 3 Function button 6 4 3 1 Manual function 6 4 3 2 Factory reset 6 5 Application description line coupler 7 6 ETS Parameters line coupler 7 6 1 Settings 7 6 2 General 8 6 3 Main line 8 6 4 Sub...
Страница 4: ...ally addressed telegrams in this document named Physical telegrams or according to the built in filter tables for group oriented communication Group telegrams Compared to other similar products the 01...
Страница 5: ...dress filtering status LED 7 Programming LED A Function button B Program button C KNX main line D KNX sub line 3 1 Installation example 01501 2 POWER SUPPLY UNIT L N AUX KNX 30V KNX 120 240V 50 60Hz 3...
Страница 6: ...e With the Programming button the device can be switched between Normal Mode and Program Mode To download the physical address to the device this function is essential After the download the 01504 2 a...
Страница 7: ...er that is set by ETS With the parameters Repetitions if errors this function can be adjusted separately for both con nected lines The default settings of these parameters should be retained 6 ETS Par...
Страница 8: ...f automatically Manual function disabled pass all telegrams pass physical telegrams pass group telegrams pass all telegrams Telegram routing configuration for the Manual Function Fig 5 General Fig 6 M...
Страница 9: ...3 Depending on the physical address only Physical telegrams are routed Physical Repetition when errors on main line 1 no 2 normal 3 reduced normal If a transmission error e g due to missing receiver i...
Страница 10: ...filter 1 All group telegrams are transmitted 2 No group telegram is transmitted 3 Only group telegrams entered in the filter table are routed ETS3 4 produces the filter table automatically Sub group t...
Страница 11: ...Line repeater has to be downloaded to the device Under the Information tab this configuration can be changed by the menu Change Application Program After changing the configuration the filter table e...
Страница 12: ...ams will be repeated only once Group Repetition when errors on main line 1 no 2 normal 3 reduced reduced If a transmission error e g due to missing receiver is found after sending a Group telegram on...
Страница 13: ...d up to three times 3 Physical telegrams will be repeated only once Group Repetition if errors on the sub line occur 1 no 2 normal 3 reduced reduced If a transmission error e g due to missing receiver...
Страница 14: ...Viale Vicenza 14 36063 Marostica VI Italy www vimar com 01504 2 EN 03 2102...