6.3 Device Info
After accessing the web front-end the Device Info tab appears . General information about current device parameters (addresses, names, software versions) is shown
here .
Figure 21: Device Info Tab
6.4 KNX
KNX-specific addresses are shown here . Settings can easily be checked . With a click on “On”, Programming Mode can be activated (same as a Programming Button
press) . Together with the Device Info tab, this function is useful to distinguish the regarded device (having a certain IP address, MAC address and serial number) from
other similar network devices .
The Individual Address, the four Individual Addresses for Tunneling (additional tunneling addresses), routing multicast address, serial number of 01548 and a last-
60-minutes KNX busload diagram (web browser must support SVG graphics) are visible . The red curve shows the maximum busload on TP and the green one shows
the average busload on TP .
Figure 22: KNX Tab
For showing the busload diagram, the web browser must support SVG graphics .
For IP Tunneling, four Individual Addresses can be set . Setting a different Individual Address for every tunneling channel via the web front-end is relevant for ETS versions
lower than 5 .7 . In this case, the first tunneling address must be set in the “Individual Address” field of the ETS Bus Connections window . With a click on “Set” the other
ones consecutively follow the first one . Reason is tunneling channels using the same Individual Address can cause a reduction of usable connections . With the Set but-
ton they can be reassigned to have differing Individual Addresses .
Before reassigning with using the Set button, it must be made sure these addresses do not exist in the project or the installation and clients do not loose connectivity
due to reassignment .
When Security is active, it is highly recommended to assign the additional Individual Addresses only by ETS projects and configuration downloads (see chapter
“5 .4 IP (Secure) Tunneling Address Assignment”) .