NT00000582-PILOT-PARC-MAITRE-AN-200723
5.
MODBUS COMMUNICATION
PILOT PARC is a slave on the link.
TCP / IP communication - use a CAT5 Ethernet cable with 8 pin RJ45 connector.
Factory controller IP adress = 192-168.0.2 - display of the current address at the bottom right of the screen
by default.
Port number to fill in: 502.
Table of registers (16 Bits Holding Registers):
Description
R/W
Read/write
Register
address
Decimal
value of
register
Bits
Register descriptions / bits*
Stop / Comfort low speed
running
W
1200**
1/2/4
B08
I1B = comfort low speed request
0 : Stop
1 : LS run
Stop / Comfort high speed
running
W
B09
I2B = comfort high speed request
0 : Stop
1 : HS run
Comfort mode fan(s)
forced stop asked
W
B10
I3B = Comfort mode fan(s) forced stop asked
0 : Run
1 : Stop asked
Timing (s.) from LS before
HS
R/W
1201
0-25
! Respect 0 - 25 s. range
Controller input states
R
1202
B08 I1B = comfort low speed asked
R
B09 I2B = comfort high speed asked
R
B10 I3B = Comfort mode fan forced stop asked
R
B11
I4B = 0 = smoke extraction asked
R
B12 I5B = reset asked
R
B13 I6B = 0 = motor 1 thermal relay fault
R
B14 I7B = 0 = motor 2 thermal relay fault***
R
B15 I8B = 0 = motor 1 slave thermal relay fault
R
B00 I1E = 0 = motor 2 slave thermal relay fault***
R
B01 I2E = Fireman stop asked
R
B02 I3E = 0 = external safety switch open
R
B03
I4E = 0 = HS airflow controller fault
Controller output states
R
1203
B08 Q1B = fault indicator
R
B09
Q2B = smoke extraction indicator (blinking -
fireman stop asked)
R
B10 Q3B = low speed motor 1
R
B11
Q4B = high speed motor 1
R
B14 Q1E = auxiliary motor run
R
B15 Q2E = high speed auxiliary motor
R
B12 Q3E = low speed motor***
R
B13 Q4E = high speed motor***
Smoke extraction active
R
1204
0/1
B08
Correspond to ""Q2B = 1 et Q4B = 1""
(+Q4E = 1 if 2 motors unit)
* 2 modules make up the controller: a base (B) + an extension (E), references B and E included in the designations of the inputs.
Example: I1B = input I1 of the Base module (EASY-E4-UC-12RC1) / Q1E = Q1 output of the Extension module (EASY-E4-UC-
8RE1).
** Activation of these inputs has priority over their physical state according to the following logic:
- Priority fan (s) stop = high priority.
- High speed operation with priority over low speed (modbus or physical).
***MASTER PARK PILOT versions 2 engines only.