NT-50906901-KSDR-ECOWATT-48-88-120-AN-170907
5/68
ENGLISH
2. PRESENTATION OF RANGE - PRODUCT
2.1 Range
Use:
Supply of fresh air into buildings with heating or cooling. Installation on stands or attached by
brackets, either indoors or outdoors.
3 sizes :
48 (4 800 m
3
/h), 88 (8 800 m
3
/h), 120 (14 000 m
3
/h).
8 Models :
•
KSDR ECOWATT
®
-
EI:
electric heater integrated.
-
EC:
heating water coil integrated.
-
EF:
cooling water coil integrated.
-
ER:
reversible heating/cooling water coil integrated.
-
ECF:
heating and cooling water coils integrated.
-
EX:
direct expansion coils.
-
EG:
run around coil integrated.
-
EGC:
run around coil and heating coil integrated.
2 Confi gurations:
•
EXD:
External arrangement, right hand access and connection sides, in air direction.
•
EXG:
External arrangement, left hand access and connection sides, in air direction.
Communicating controller assembled/wired ready to be connected:
Variable fl ow (VAV), constant fl ow (CAV), constant pressure (COP).
Temperature adjustment by integrated CORRIGO controller specifi c to VIM.
Modbus communicating on RS485 port and Bacnet IP on TCP/IP port.
ETD remote touch control included.
Example of complete designation:
KSDR ECOWATT
®
EI 48 EXD CORRIGO Bat Elec Tri 45kW CTA
2.2 Products - Main components
Coil/heater arrangements: electrical (EI), hot water (EC), cold (EF), reversible (ER) or hot and cold water (ECF):
EI Model
Marking
Designation
8
9
10
11
1
2
3
5
4
6
7
1
2
3
4
5
6
7
8
9
10
11
Pre fi lter
Filter
Plug fan
Filter clogging pressure switch
Control board
Electrical heater
Safety thermostats
Outdoor air temperature sensor
Supply air temperature sensor
Roof insulation
Bottom insulation