19/48
NT00000603-JBRB-ECOWATT-PR-AN-191202
5.5.3
Relay electrical connection - Model 30 to 92 three-phase
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19
+24V
Fire
+24V
Start/Sto
p
Speed-Output
GN
D
+24V
GN
D
An
2
+10V
GN
D
An
1
NO
CO
M
NC
Relay fault
Ventilation fault wiring
Open contact - Stop of the fan
Invento
A
B
PE
U
V
W
PE
L1
L2
L3
Unit status
Relay status
“Normal” operation
NO
Power supply shut off
NC
On/Off contact - The wheel is stationary but the conductor is powered up
NC
Phase loss - In case of phase loss, the wheel may continue to turn
NC check-list
5.6 Electrical connection of optional TCOM remote control
The remote control covers all the RMEC front panel functions:
• It includes a 20-alphanumeric character, 2-line backlit LCD display, and a navigation button in the
Menu. 2 green/red LEDs indicate the communication activity between the RMEC and the remote
control.
Protection index (PI): 21.
Operating environment:
•
Temperature 0°C to + 40°C without condensation.
•
30 to 80% relative humidity.
It can be connected to the RMEC in two ways according to use:
Temporary connection:
Standard application case = for configuration of the product, when the RMEC display is not clearly visible (e.g.
installation in suspended ceiling).
•
Shut off the RMEC power supply.
• Remove the waterproof stopper from the RMEC front panel to access the jack socket
The RMEC’s
protection index then switches from IP55 to IP21.
•
A 1m-long jack cable is supplied with the remote control: clip its HE13 socket to the back of the re
-
mote control, see plan below, and insert its jack plug into the RMEC’s jack socket.
• Power the RMEC back up.
•
Configure the RMEC using the remote control.
•
Once you’ve finished, shut off the RMEC’s power supply.
• Unplug the jack plug from the RMEC.
• Replace the RMEC front panel waterproof stopper to restore its protection index to IP55.
• Power the RMEC back up.
N.B.: plugging the remote control in or unplugging it from the RMEC without shutting off its power supply caus
-
es a temporary short-circuit, which resets the microcontroller. This does not present any physical risk for the
worker, but should be avoided because it strains the electronic components.