Respect a distance of 2 times the diameter between the heater and other network components. particularly
filters.
Respect a distance of 100mm between the heater and surrounding materials.
Air supply devices (vents / diffusers) must not be able to be totally blocked.
Electrical installation
Include a single-pole switch on the power supply with spacing of at least 3mm in a stationary system.
Make sure that the network fan turns on before or at the same time as the heater starts heating. Include a
post-ventilation delay so that the fan stops after the heater is shut off. (block diagram § "4. ELECTRICAL
CONNECTION".
The device is originally equipped with two safety thermostats to avoid overheating.
An automatic reset safety thermostat (50°C) and a manual reset safety thermostat (100°C) located on the
cover.
They must control an external contactor (not supplied) that shuts off the mains power supply
in case of activation.
Attention
: the control circuit is not galvanically isolated from the device’s power circuit.
Electrical wires and cables
• Max wire diameter for control connections: up to 4mm
2
.
• Max cable diameter for power supply:
10mm
2
16mm
2
Mono 230V
≤ 4,5kW
˃ 4,5kW
Tri 400V
≤ 15kW
˃ 15kW
4.
ELECTRICAL CONNECTION
4.1 BATE-R010 Single-phase - Power < 4kW
1 phase power supply
airflow
controller
according to NF C 15-100 standard
auto
reset
manual
reset
Command signal
L1
N
50°C
θ
100°C
θ
B
C
PTC
BATE-R010
PE
9
10
0...10Vcc
N
L
230V 50Hz
<4kW
Equipment
Included
Optional
BATE R010
Electrical heater
MCR1
Post-ventilation delay