Measuring Purge Drain Rate

Install the provided 1/2” plug x 3/4” elbow as shown to 

begin piping the drain line.

This fitting provides easy access for measuring the drain 

purge rate when the unit is operating by removing the 

1/2” plug.

WATER QUALITY PURGE CONTROL

PURGE ADJUSTMENT 

It is recommended to measure or refer to the local water conditions with regard to Hardness and Alkalinity to help you with the best 

water purge rate selection (Figure 6)

Use the “Purge Adjustment Valve” to control the amount of water that is purged from the unit during operation (Figure 9, part 10)

note: The Purge Adjustment Valve is shipped to provide a large purge rate at startup. This large purge rate will help flush and clean 

the purge assembly. Refer to Figure 6 and Figure 8 to select your purge rate and adjust as needed. 

Using the Purge Adjustment chart (Figure 8), plot your units application and find the suggested ounces per min purge rate. This 

is measured at the provided plug elbow just outside the unit (Figure 7).  Slowly adjust the Purge Adjustment Valve from a closed 

position to a open position to redudce the purge drain rate. Allow the system to stabilize and measure the purge drain for your 

 

target amount, adjust as needed.  

Suggested start up and measurement techniques

T

he purge rate can vary a little when first installed. The purge rate is adjusted by using the purge valve located just below the purge 

collector piping.  It is best to measure the drain serveral times durig the start up in order to average the purge rate.

The purge valve adjustments should be done slowly as it will take 30 seconds for the internal 

water level to adjust to the new setting.After several minutes measure the purge rate 

using the plug elbow as a convenient location. It is recommended to take several 1 minute

 

measurements and average the results. A good technique is to take 3 one-minute measurements  

over 5-10 minutes of operation. If adjustment is required, make small adjustments and recheck 

results over several tests to ensure you have consistency.

Helpful tips
When unsure of the water conditions use the maximum purge rate. The Purge

 

Adjustment 

control table assumes the use of Nu-Calgons EvapTreat food grade Polyphosphate water treatment 4173-04.

The “Purge adjustment valve” allows you to set the correct amount of purge drain water. The local water conditions (Hardness and 
Alkalinity) will help to predict the best setting. (Figure 6 & Figure 8) 

note: During annual service, review the condition of the pump screen for help in determining your sump water condition. If you see a 

lot of 

scale forming on the pump screen, this would indicate that you should increase the purge rate up to the maximum setting for your model 

and your existing water condition. Measure and test the purge rate using the Adjustment valve and by measuring the purge water from the 

drain plug to the correct pruge target.

All water control information includes the use of Nu-Calgon EVAPTreat water conditioning. This is a food grade polyphosphate used 

to 

keep minerals suspended in the water until purged. The control table provided includes the use of the EVAPTreat water conditioning. This 

product is replaced at the beginning of each air conditioning season.

Figure 7.

  

1/2” pluG X 3/4” elbow in drain line

3/4” purge 

drain

1/2” plug

Содержание AquaChill AQV

Страница 1: ......

Страница 2: ...manufactured by villara corporation REV 4 5 18 AQV homeowner s operation manual Now You re Cooler ...

Страница 3: ... by 25 40 We are passionate about our customers and assisting in the environmental concerns of today The AquaChill is an important step towards our goal of complete customer satisfaction and doing our part to conserve energy Villara Building Systems is honored and delighted to provide this energy efficient technology to you Please contact us if you have any questions or concerns regarding your new...

Страница 4: ......

Страница 5: ......

Страница 6: ...owner quick tips 7 Electrical wiring diagram 8 System diagram 8 Parts Diagram 9 Warranty information 10 Villara Corporation works continually to improve its products As a result the design and specifications of the AquaChill unit may vary slightly Please contact Villara s Manufacturing Department at 916 646 2700 for specific information on current product design and specifications Statements and o...

Страница 7: ... Custom Polyethylene cabinet with UV resistance Sound absorbing construction materials Easy access door for servicing Water Requirements Unit requires a water shut off valve and 1 4 water line Safety Considerations WARNING or DANGER denotes safety alerts regarding hazards that will result in severe injury or death CAUTION denotes alerts to unsafe practices that can result in minor personal injury ...

Страница 8: ...or prov inces do not allow limitations on how long an implied warranty or condition last so the above may not apply to you The expressed warran ties made in this warranty are exclusive and may not be altered enlarged or changed by any distributor dealer or other person whatsoever Villara Corporation will not be responsible for 1 Damage or repair required as a consequence of faulty installation or ...

Страница 9: ... COIL ASSEMBLY 5 T 8 ROW 8 TOP OF MAIN BODY OF CASING PARTS DESCRIPTION ITEM AQUACHILL PARTS DIAGRAM PARTS BREAKDOWN FRONT VIEW 1 ELECTRICAL CONTROL BOX 2 CONTACTOR 3 TIME DELAY 4 CAPACITOR COMPRESSOR FAN 5 COMPRESSOR SIZE PER MODEL 6 VALVE CARRIER LIQUID LINE 7 VALVE CARRIER SUCTION LINE 8 BALL VALVE FLOAT ASSEMBLY 9 NU CALGON PURGE VAP WATER TREATMENT 10 DRIP DRAIN PURGE ASSEMBLY 11 LOW LEVEL PR...

Страница 10: ...ves performance Following is a step by step procedure for normal sump cleaning Regular maintenance and or service is the key to long trouble free performance from your unit The following schedule will help you maintain an efficient unit with good appearance Adhering to the suggested schedule of component replacement at the start of the season will reduce in season maintenance requirements CAUTION ...

Страница 11: ...ake sure to turn off the electrical disconnect on the wall before working on the unit When you put your hands in the unit you run the risk of injury if the unit is accidentally turned on from inside the house Never wear slick soled shoes when working on a roof You may slip when you least expect it PERIODIC SERVICE OR MAINTENANCE Service Needs Semi Annual Start up Semi Annual Shut down Rinse off fa...

Страница 12: ...AIR WIRING DIAGRAM DANGER of serious injury or death Disconnect all electricity before servicing WARNING There may be multiple disconnects on each unit and all disconnects must be turned off Check local codes for wiring Wiring connections and adjustments should be made ONLY by qualified persons Amperage must not exceed total nameplate ratings of the electrical equipment SYSTEM DIAGRAM Ultra effici...

Страница 13: ...e a water valve on the copper water line it is critical that this valve is on during the air conditioning season The base pan has a brass drain plug The drain cap is unscrewed to drain the reservoir during servicing or to drain the reservoir during winter During the summer the drain cap should be in place and tightened properly Preparing your AquaChill for Winter At the end of the cooling season w...

Страница 14: ... up connection to non softened water 4 Add EVAPTreat water treatment EVAPTreat product lasts one season 1 Drain flush and clean reservoir Check purge flow operation Refer to unit water treatment bulletin 1 Flush or rinse out base until soap residue is removed TROUBLE SHOOTING Possible Causes 1 Thermostat setting 2 No electrical power 3 Fuse blown 4 Circuit breaker tripped 5 Faulty wiring or shorts...

Страница 15: ...15 20minutes forthewatertemperaturetoreach a stable temperature when the unit is operating AQV30X0101 piston size 65 AQV41X0101 piston size 73 WATER TREATMENT Chemical water treatment is usually not required The chlorine and other treatments added to city water are generally more than adequate biocide treatments for residential applications The purge control is provided to reduce the buildup of mi...

Страница 16: ...rgevalveadjustmentsshouldbe done slowly as it will take 30secondsfortheinternal water level to adjust to the new setting After several minutes measure the purge rate using the plug elbow as a convenientlocation It is recommended to take several 1 minute measurementsandaveragetheresults Agoodtechniqueistotake3one minutemeasurements over5 10minutesofoperation Ifadjustmentisrequired makesmalladjustme...

Отзывы: