STANDARD RESPONSE 

ELO UPRIGHT SPRINKLER

VK530 

(STORAGE-DENSITY/AREA)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page.

Form No. F_010692    21.09.16     Rev 21.1

Page 3 of 5

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature 

Classification

Sprinkler Nominal

 

Temperature Rating

1

Maximum Ambient

 

Ceiling Temperature

2

Bulb Color

Ordinary

155 °F (68 °C)

100 °F (38 °C)

Red

Intermediate

175 °F (79 °C)

150 °F (65 °C)

Yellow

Intermediate

200 °F (93 °C)

150 °F (65 °C)

Green

High

286 °F (141 °C)

225 °F (107 °C)

Blue

Sprinkler Finishes:

 Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT

Corrosion-Resistant Coatings

3

:

 White Polyester, Black Polyester, and Black PTFE in all temperature ratings. ENT in all temperature 

ratings except 135°F (57°C). Wax-Coated Brass for sprinklers with the following temperature ratings:

  155 °F (68 °C) Lt. Brown Wax    175 °F (79 °C) Brown Wax     200 °F (93 °C) Brown Wax    286 °F (141 °C) Dk. Brown Wax

4

 

Footnotes

1

 The sprinkler temperature rating is stamped on the deflector. 

2

 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. 

Refer to specific installation standards.

3

 The corrosion-resistant and corrosion proofing coatings have passed the standard corrosion test required by the approving agencies indicated in the 

Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that 

the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed 

exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester, ENT, and PTFE coatings. For PTFE coated open sprinklers only, 

the waterway is coated. For all ENT coated sprinklers, the waterway is coated.

4

 Wax melting point is 170 °F (76 °C) for 286 °F (141 °C) temperature rated sprinklers.

Figure 1:  Sprinkler VK530 and Wrench 

05118CW/B

Protective 

clip

Wrench

flat

Figure 2:  Sprinkler VK530 Dimensions

1-3/4” (45 mm)

2-5/16” 

(59 mm)

3/4” NPT

(20 mm)

Содержание VK530

Страница 1: ...se sprinklers may be ordered and or used as open sprin klers glass bulb and pip cap assembly removed on deluge systems Refer to Ordering Instructions below 2 LISTINGS AND APPROVALS cULus Listed Category VNIV FM Approved Class 2009 Refer to Approval Chart 1 and Design Criteria on page 3 for cULus Listing requir ments and refer to Approval Chart 2 and Design Criteria on page 4 for FM Approval requir...

Страница 2: ...s Refer to Table 1 Accessories Also refer to the Viking website Sprinkler Wrenches A Standard Wrench Part No 05118CW B available since 1981 Sprinkler Cabinets A Six head capacity Part No 01724A available since 1971 B Twelve head capacity Part No 01725A available since 1971 4 INSTALLATION Refer to appropriate NFPA Installation Standards 5 OPERATION During fire conditions when the temperature around...

Страница 3: ...t Brown Wax 175 F 79 C Brown Wax 200 F 93 C Brown Wax 286 F 141 C Dk Brown Wax4 Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Other limits may apply depending on fire loading sprinkler location and other requirements of the Authority Having Jurisdiction Refer to specific installation standards 3 The corrosion resistant and corrosion proofing coatings h...

Страница 4: ...technical data the appropriate standards of NFPA LPCB APSAD VdS or other similar organizations and also with the provisions of governmental codes ordinances and standards whenever applicable Approval Chart 1 UL Standard Response Extra Large Orifice Upright Sprinkler VK530 Maximum 175 PSI 12 Bar WWP Base Part Number1 SIN Sprinkler Style Thread Size Nominal K Factor Overall Length Listings and Appro...

Страница 5: ...t the time of printing Other approvals may be in process 4 FM Approved as corrosion resistant DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements Standard Response Extra Large Orifice Upright Sprinkler VK530 is FM Approved as a standard response upright Non Storage sprinkler and as a standard response upright Storage sprinkler as indicated in the FM Approval Guide For ...

Страница 6: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 7: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 8: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 9: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 10: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Страница 11: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Страница 12: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Страница 13: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: