QUICK RESPONSE 

ORDINARY HAZARD DRY 

HSW FUSIBLE LINK  

SPRINKLERS (8.0K)  

(VK2843, VK2883, & VK2923)

TECHNICAL DATA

Page 8 of 8

Form No. F_022717     18.11.01     Rev 18.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Figure 8:  Dry Horizontal Sidewall Sprinkler Minimum Barrel Length Based on Ambient Temperature in the Protected Area 

(Adjustable Standard Dry HSW Sprinkler is Shown)

Seal the clearance space around the sprinkler to avoid leakage of 

air into the protected area and consequent formation of condensate 

around the sprinkler frame, which could inhibit operation or cause 

premature operation. Refer to Figure 9.

If humidity and temperature differential causes condesation on the 

exposed dry sprinkler barrel, consider wrapping the exposed barrel 

with insualtion, foam insulating tape, or equivalent. 

Install the threaded end of the sprinker into a 1” NPT outlet of a 

malleable iron

 tee fitting per ANSI B 16.3 (Class 150) 

or 

cast iron

 threaded tee fitting per ANSI 16.4 (Class 125) only.

Exposed Barrel

Outer surface of wall

Ambient Temperature 

of the Protected Area* 

at the Discharge End 

of the Sprinkler

Exposed Barrel Ambient Temperature

40 

°

F (4 

°

C)

50 

°

F (10 

°

C) 60 

°

F (16 

°

C)

Exposed Minimum Barrel Length**  

Face of the Tee to the Outer Surface of the Wall
 

 Inches (mm)     Inches (mm)     Inches (mm)

40 °F (4 °C)

0

0

0

30 °F (-1 °C)

0

0

0

20 °F (-7 °C)

4 (100)

0

0

10 °F (-12 °C)

8 (203)

1 (25)

0

0 °F (-18 °C)

12 (305)

3 (76)

0

-10 °F (-23 °C)

14 (356)

4 (102)

1 (25)

-20 °F (-29 °C)

14 (356)

6 (152)

3 (76)

-30 °F (-34 °C)

16 (406)

8 (203)

4 (102)

-40 °F (-40 °C)

18 (457)

8 (203)

4 (102)

-50 °F (-46 °C)

20 (508)

10 (254)

6 (152)

-60 °F (-51 °C)

20 (508)

10 (254)

6 (152)

*    The protected area refers to the area below the ceiling, the ambient 

temperature is the temperature at the discharge end of the sprinkler. 

For protected area temperatures that occur between the values 

listed, use the next cooler temperature. 

**   The minimum reuired barrel length is not the same as the “A” 

dimension. Refer to Figures 3, 5, and 6 for the “A” Dimension. 

Exposed minimum barrel lengths aer inclusive up to 30 mph wind 

velocities.

Figure 9:  Dry Sprinkler Seal (Adjustable Standard Dry HSW Sprinkler is Shown)

Seal Part Number 

19398M/W or 

equivalent method.

Clearance Opening

Insulated wall

Insulated wall

Seal

Dry sprinkler seal on the exterior of the wall

Dry sprinkler seal within the wall

Replaces Form No. F_022717 Rev 18.1

(Added P65 Warning.)

Содержание VK2843

Страница 1: ...olyester finish may change color This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such All sprinklers installed in corrosive environments s...

Страница 2: ...Horizontal Sidewall up to 62 1 575 mm Plain Barrel Dry Horizontal Sidewall up to 64 1 626 mm Contact the manufacturer for more information Finish Suffix Brass A Chrome F and White Polyester M W Temper...

Страница 3: ...1 2 to 45 1 2 38 1 mm to 1 156 mm 2 Chrome or White Polyester with A dimensions 3 1 4 to 47 1 2 82 5 mm to 1 207 mm 3 Chrome or Brass with A dimensions 3 to 47 76 2 mm to 1 194 mm Footnotes 1 Part nu...

Страница 4: ...Fusible Link Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers Designed for use in Light a...

Страница 5: ...5 mm shorter than the A Dimension To locate the deflector at the maximum distance from the wall with no adjustment available order the standard dry horizontal sidewall sprinikler 1 25 mm longer than t...

Страница 6: ...1 16 27 mm 5 Escutcheon outer diameter 3 1 16 78 mm 6 Top of deflector to centerline 5 8 16 mm Determining the A Dimension Adustable Recessed HSW Sprinkler with Model E 1 Escutcheon 1 Determine the d...

Страница 7: ...to deflector distance 2 1 4 57 mm 4 Top of deflector to centerline 5 8 16 mm 5 Pipe outside diameter Same as 1 13 mm Schedule 40 pipe 1 5 16 33 mm Determining the A Dimension Plain Barrel Dry HSW Spri...

Страница 8: ...eaded tee fitting per ANSI 16 4 Class 125 only Exposed Barrel Outer surface of wall Ambient Temperature of the Protected Area at the Discharge End of the Sprinkler Exposed Barrel Ambient Temperature 4...

Отзывы: