Viking VK2843 Скачать руководство пользователя страница 6

QUICK RESPONSE 

ORDINARY HAZARD DRY 

HSW FUSIBLE LINK  

SPRINKLERS (8.0K)  

(VK2843, VK2883, & VK2923)

TECHNICAL DATA

Page 6 of 8

Form No. F_022717     18.11.01     Rev 18.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Figure 5:  Adjustable Recessed Ordinary Hazard Dry HSW Fusible Link Sprinkler with the Model E-1 Escutcheon

Figure 4:  Adjustable Standard Escutcheon Installation

Ref Variable Parameter

Minimum

Maximum

1

Wall opening

2-1/8” (54 mm)

2-1/2” (64 mm)

2

Deflector to ceiling distance

4” (102 mm)

12” (305 mm)

3

Deflector to wall distance

1-7/8” (48 mm)

2-1/2” (64 mm)

Ref Fixed Parameter

Value

4

Escutcheon depth (Model E-1)

1-1/16” (27 mm)

5

Escutcheon outer diameter

3-1/16” (78 mm)

6

Top of deflector to centerline

5/8” (16 mm)

Determining the “A” Dimension: Adustable Recessed HSW Sprinkler with Model E-1 Escutcheon

1. 

Determine the distance from the face of the tee to the finished face of the wall.

2.  Round to the nearest 1/4” (16 mm) between 3-1/4” (83 mm) and 47-1/2” (1,207 mm).

NOTE: The sprinkler will be recessed approximately 5/16” (8 mm) with 5/8” (16 mm) horizontal adjustment available.

Step 1: 

Align the slot in the 

escutcheon with the horizontal 

surface of the deflector as shown.

SLOT

DEFLECTOR

Step 2:

 Push the rounded end 

of the slot against the near edge 

of the deflector.Slighty rotate the 

escutcheon horizontally and push 

the far side of the escutcheon past 

the deflector, toward the sleeve. 

Step 3:

 Re-align the escutcheon 

with the sprinkler barrel and 

continue pushing it toward the 

sleeve.

Step 4:

 Push and rotate the 

escutcheon onto the sleeve 

and, if desired, orient the slot 

toward the top to minimize 

visibility.

2

6

3

4

3

Finished W

all

Finished 

Ceiling

A

5

1

Содержание VK2843

Страница 1: ...olyester finish may change color This natural discoloration over time is not in itself an indication of corrosion and should not be treated as such All sprinklers installed in corrosive environments s...

Страница 2: ...Horizontal Sidewall up to 62 1 575 mm Plain Barrel Dry Horizontal Sidewall up to 64 1 626 mm Contact the manufacturer for more information Finish Suffix Brass A Chrome F and White Polyester M W Temper...

Страница 3: ...1 2 to 45 1 2 38 1 mm to 1 156 mm 2 Chrome or White Polyester with A dimensions 3 1 4 to 47 1 2 82 5 mm to 1 207 mm 3 Chrome or Brass with A dimensions 3 to 47 76 2 mm to 1 194 mm Footnotes 1 Part nu...

Страница 4: ...Fusible Link Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers Designed for use in Light a...

Страница 5: ...5 mm shorter than the A Dimension To locate the deflector at the maximum distance from the wall with no adjustment available order the standard dry horizontal sidewall sprinikler 1 25 mm longer than t...

Страница 6: ...1 16 27 mm 5 Escutcheon outer diameter 3 1 16 78 mm 6 Top of deflector to centerline 5 8 16 mm Determining the A Dimension Adustable Recessed HSW Sprinkler with Model E 1 Escutcheon 1 Determine the d...

Страница 7: ...to deflector distance 2 1 4 57 mm 4 Top of deflector to centerline 5 8 16 mm 5 Pipe outside diameter Same as 1 13 mm Schedule 40 pipe 1 5 16 33 mm Determining the A Dimension Plain Barrel Dry HSW Spri...

Страница 8: ...eaded tee fitting per ANSI 16 4 Class 125 only Exposed Barrel Outer surface of wall Ambient Temperature of the Protected Area at the Discharge End of the Sprinkler Exposed Barrel Ambient Temperature 4...

Отзывы: